Enhancing the Sensitivity of Power Transformer Differential Protection in Power Systems.
View through CrossRef
Differential protection is a fundamental protection scheme used to detect and isolate internal faults in power transformers. It works on the principle of comparing the currents entering and leaving the protected zone (transformer). Under normal operating conditions or external fault, the current flowing into the transformer should equal the current flowing out, with taking into consideration the transformer’s turn ratio. Under normal conditions, the differential current between primary and secondary sides should be close to zero, a small difference value may exist due to transformer magnetizing current, current transformer (CT) measurement errors and Tap changer position. The Tap changer position will cause the transformer turn ratio errors which is a cause to give trip signal from differential relay to the transformer circuit breaker if it is not compensating in the differential protection relay. Using the new technique of on-load tap changer (OLTC) position to reduce the turn ratio error in order to improve the differential protection sensitivity, the proposal technique includes new equations that are simulated by PSCAD/EMTDC software. It can be clearly shown that the proposed technique will reduce the turn ratio error to the minimum value with comparing to the conventional schemes.
Salahaddin University - Erbil
Title: Enhancing the Sensitivity of Power Transformer Differential Protection in Power Systems.
Description:
Differential protection is a fundamental protection scheme used to detect and isolate internal faults in power transformers.
It works on the principle of comparing the currents entering and leaving the protected zone (transformer).
Under normal operating conditions or external fault, the current flowing into the transformer should equal the current flowing out, with taking into consideration the transformer’s turn ratio.
Under normal conditions, the differential current between primary and secondary sides should be close to zero, a small difference value may exist due to transformer magnetizing current, current transformer (CT) measurement errors and Tap changer position.
The Tap changer position will cause the transformer turn ratio errors which is a cause to give trip signal from differential relay to the transformer circuit breaker if it is not compensating in the differential protection relay.
Using the new technique of on-load tap changer (OLTC) position to reduce the turn ratio error in order to improve the differential protection sensitivity, the proposal technique includes new equations that are simulated by PSCAD/EMTDC software.
It can be clearly shown that the proposed technique will reduce the turn ratio error to the minimum value with comparing to the conventional schemes.
Related Results
Automatic Load Sharing of Transformer
Automatic Load Sharing of Transformer
Transformer plays a major role in the power system. It works 24 hours a day and provides power to the load. The transformer is excessive full, its windings are overheated which lea...
High frequency modeling of power transformers under transients
High frequency modeling of power transformers under transients
This thesis presents the results related to high frequency modeling of power transformers. First, a 25kVA distribution transformer under lightning surges is tested in the laborator...
ANALISIS PENGARUH MASA OPERASIONAL TERHADAP PENURUNAN KAPASITAS TRANSFORMATOR DISTRIBUSI DI PT PLN (PERSERO)
ANALISIS PENGARUH MASA OPERASIONAL TERHADAP PENURUNAN KAPASITAS TRANSFORMATOR DISTRIBUSI DI PT PLN (PERSERO)
One cause the interruption of transformer is loading that exceeds the capabilities of the transformer. The state of continuous overload will affect the age of the transformer and r...
LIFE CYCLE OF TRANSFORMER 110/X KV AND ITS VALUE
LIFE CYCLE OF TRANSFORMER 110/X KV AND ITS VALUE
In a deregulated environment, power companies are in the constant process of reducing the costs of operating power facilities, with the aim of optimally improving the quality of de...
PLC Based Load Sharing of Transformers
PLC Based Load Sharing of Transformers
The transformer is very expensive and bulky power system equipment. It runs and feed the load for 24 hours a day. Sometimes the load on the transformer unexpectedly rises above its...
Simulation modeling study on short circuit ability of distribution transformer
Simulation modeling study on short circuit ability of distribution transformer
Abstract
Under short circuit condition, the oil immersed distribution transformer will endure combined electro-thermal stress, eventually lead to the mechanical dama...
Uji Performa Trafo E-I dengan Variasi Rapat Fluks pada Sumber Tegangan Non-Sinusoidal
Uji Performa Trafo E-I dengan Variasi Rapat Fluks pada Sumber Tegangan Non-Sinusoidal
In the industrial field, transformers are used as a step-up voltage and are used as a step-down level. In a loaded transformer, the power that comes out of the transformer (transfo...
Adaptive ANN based differential protective relay for reliable power transformer protection operation during energisation
Adaptive ANN based differential protective relay for reliable power transformer protection operation during energisation
Power transformer is the most expensive equipment in electrical power system that needs continuous monitoring and fast protection response. Differential relay is usually used in po...