An Intelligent Model and Simulation of High Voltage and Medium Voltage Transmission Line Protection Scheme Using Time Overcurrent Relay Optimization Settings

View through CrossRef
Abstract A new method for optimizing overcurrent relay (OCR) settings and coordination in interconnected power systems was developed. The method considers factors such as feeder impedance equivalences, phase-to-phase fault currents, current settings of 110kV incoming and 15kV outgoing feeders, and operating times for relay characteristics (standard, very, and extremely inverse of overcurrent relay). The maximum fault current of the interconnected power grids is also considered. Power system parameters like X/R ratio, current transformer ratio, transmission line length, resistances, inductances, full load current, line capacity, CT ratio for outgoing feeders, grid frequency, and real power are also considered. To ensure safety and rapid operation of overcurrent relays, settings such as pickup value, time setting multiplier (TMS), and OCR characteristics are carefully considered. The results show that the OCRs coordination interval time to fastest clear faults range from 0.0927 sec-0.062 sec to 0.0764 sec-0.0661 sec for extremely, very, and standard inverse relays, respectively.
Title: An Intelligent Model and Simulation of High Voltage and Medium Voltage Transmission Line Protection Scheme Using Time Overcurrent Relay Optimization Settings
Description:
Abstract A new method for optimizing overcurrent relay (OCR) settings and coordination in interconnected power systems was developed.
The method considers factors such as feeder impedance equivalences, phase-to-phase fault currents, current settings of 110kV incoming and 15kV outgoing feeders, and operating times for relay characteristics (standard, very, and extremely inverse of overcurrent relay).
The maximum fault current of the interconnected power grids is also considered.
Power system parameters like X/R ratio, current transformer ratio, transmission line length, resistances, inductances, full load current, line capacity, CT ratio for outgoing feeders, grid frequency, and real power are also considered.
To ensure safety and rapid operation of overcurrent relays, settings such as pickup value, time setting multiplier (TMS), and OCR characteristics are carefully considered.
The results show that the OCRs coordination interval time to fastest clear faults range from 0.
0927 sec-0.
062 sec to 0.
0764 sec-0.
0661 sec for extremely, very, and standard inverse relays, respectively.

Related Results

Coordination of Overcurrent Relay In Distribution System
Coordination of Overcurrent Relay In Distribution System
The overcurrent phenomena are a dangerous condition that can be occurred in the electrical system and equipment. The condition of the overcurrent will cause the short-circuited cur...
Design and Construction of Inverse Time & Definite Time Overcurrent Relay Based on Arduino Uno
Design and Construction of Inverse Time & Definite Time Overcurrent Relay Based on Arduino Uno
This system is designed to detect overcurrent faults, then disconnect them from the circuit. In inverse time overcurrent relay, the relay trip time will depend on the magnitude of ...
Overcurrent Relay for Generation Distribution Utilization
Overcurrent Relay for Generation Distribution Utilization
Distributed Generation (DG) is the production of electricity from a variety of renewable energy sources that is closer to the customer and load. The addition of distributed generat...
ANALISIS PENGUJIAN RELAY PROTEKSI MENGGUNAKAN RELAY TESTING UNIT TIPE PTE-100-C PLUS
ANALISIS PENGUJIAN RELAY PROTEKSI MENGGUNAKAN RELAY TESTING UNIT TIPE PTE-100-C PLUS
Relay proteksi adalah suatu relay listrik yang digunakan untuk mengamankan peralatan-peralatan listrik terhadap kondisi abnormal. Banyaknya karakteristik beban dan penambahan beban...
Protection Relay Setting based on Overcurrent Phenomena in Commercial Building
Protection Relay Setting based on Overcurrent Phenomena in Commercial Building
Nowadays, every single distribution system needs to install an appropriate relay to keep the system safe. The operational and commonly recommended relay for distribution systems is...
Adaptive ANN based differential protective relay for reliable power transformer protection operation during energisation
Adaptive ANN based differential protective relay for reliable power transformer protection operation during energisation
Power transformer is the most expensive equipment in electrical power system that needs continuous monitoring and fast protection response. Differential relay is usually used in po...