Investigation and Analysis of Air Curtains for the Improvement of Refrigeration Energy Efficiency
View through CrossRef
The purpose of this research is to present a warm air infiltration simulation for a cold room, considering the effects of an air curtain. At present, there exist a large number of retail businesses, operating within an industry entailing high investment and competition. Therefore, retail operators must distinguish factors that are essential to lowering their costs, one of which is energy reduction. A survey of energy consumption in stores found that most used energy is due to the cooling system. Therefore, we tested the protection of cold rooms against air inflow by conducting three simulations: 1. Without an air curtain; 2. using an air curtain having a common grille; and 3. using an air curtain with a honeycomb grille. The cold room temperature was set to 1 °C, the cold room door was 200 × 100 m2, and the air curtain was installed 5 cm above the cold room door; furthermore, the velocity of air emitted from the air curtain was 6.5 m/s. Warm air infiltration simulations were carried out using SolidWorks Flow Simulation software, in order to determine the temperature change in the cold room and the airflow direction. From the results of the comparative experiments, when using the different wind grilles, there were differences in the infiltration of warm air. The honeycomb grille reduced air turbulence in the cold room more effectively than the common grille. As a result, the temperature in the cold room was consistent, and the temperature inside the cold room was maintained 10.62% lower when using a honeycomb grille compared to a common grille.
Title: Investigation and Analysis of Air Curtains for the Improvement of Refrigeration Energy Efficiency
Description:
The purpose of this research is to present a warm air infiltration simulation for a cold room, considering the effects of an air curtain.
At present, there exist a large number of retail businesses, operating within an industry entailing high investment and competition.
Therefore, retail operators must distinguish factors that are essential to lowering their costs, one of which is energy reduction.
A survey of energy consumption in stores found that most used energy is due to the cooling system.
Therefore, we tested the protection of cold rooms against air inflow by conducting three simulations: 1.
Without an air curtain; 2.
using an air curtain having a common grille; and 3.
using an air curtain with a honeycomb grille.
The cold room temperature was set to 1 °C, the cold room door was 200 × 100 m2, and the air curtain was installed 5 cm above the cold room door; furthermore, the velocity of air emitted from the air curtain was 6.
5 m/s.
Warm air infiltration simulations were carried out using SolidWorks Flow Simulation software, in order to determine the temperature change in the cold room and the airflow direction.
From the results of the comparative experiments, when using the different wind grilles, there were differences in the infiltration of warm air.
The honeycomb grille reduced air turbulence in the cold room more effectively than the common grille.
As a result, the temperature in the cold room was consistent, and the temperature inside the cold room was maintained 10.
62% lower when using a honeycomb grille compared to a common grille.
Related Results
Modern refrigeration solutions for maritime sector and marine refrigeration transport
Modern refrigeration solutions for maritime sector and marine refrigeration transport
New coming environmental regulations from International Maritime Organization put each involved actor from ship manager, ship owner to cargo owner into a hard situation for a short...
Study of Honeycomb Air Curtain for a Freezer Room to Enhance Protection against Warm Air Infiltration
Study of Honeycomb Air Curtain for a Freezer Room to Enhance Protection against Warm Air Infiltration
The objective of this research is to present the energy-saving effect of applying an air curtain to prevent the penetration of warm air through a freezer door. Retail business is h...
Assessing lead curtains’ impact on radiation protection in coronary interventions
Assessing lead curtains’ impact on radiation protection in coronary interventions
Abstract
The objective of this investigation is to assess the impact of supplementary lead curtains on the reduction of radiation dose exposure to operators during c...
METHOD FOR EVALUATING EFFICIENCY OF REFRIGERATION UNITS BASED ON SINGLE-STAGE COMPRESSION CYCLE
METHOD FOR EVALUATING EFFICIENCY OF REFRIGERATION UNITS BASED ON SINGLE-STAGE COMPRESSION CYCLE
The development of automation and programming tools is one of the priority areas determined by the State Program "National Technology Initiative," which requires the development of...
Removal of toxic vapors by oxidation: Development of laboratory test procedures for in-duct air cleaning systems
Removal of toxic vapors by oxidation: Development of laboratory test procedures for in-duct air cleaning systems
Exposure to volatile organic compounds (VOC) in workplaces can cause acute effects such as irritation of the skin, the eyes, the mouth, and the nose. Some products may also cause c...
Refrigeration
Refrigeration
Abstract
This chapter focuses primarily on refrigeration applications, which cover such diverse uses as food processing and storage, supermarket display cases, skating ri...
Energy Performance Benchmarking of Process Refrigeration Units
Energy Performance Benchmarking of Process Refrigeration Units
Abstract
Process refrigeration units are one of the major energy consumers at gas processing plants. Owing to the higher energy consumption, evaluation and benchmark...
Erratum in: "Lyudmila D. Akimova (11.08.1929–12.09.2022)"
Erratum in: "Lyudmila D. Akimova (11.08.1929–12.09.2022)"
There was a mistake in the obituary "Lyudmila D. Akimova (11.08.192912.09.2022)" published in 'Refrigeration Technology'2022;111(2) doi: 10.17816/RF112047. Previously published tex...