PERFORMANCE STUDY OF OVERVOLTAGE CUTTING BY LIGHTNING ARRESTER DUE TO LIGHTNING INDUCTION
View through CrossRef
Lightning disturbances often cause induced overvoltages on 20 kV medium voltage distribution overhead lines, which can shorten equipment life and trigger power outages. This study aims to evaluate the cutting performance of two types of lightning arresters made of ceramic and polymer in reducing lightning-induced voltage surges through high-voltage impulse testing in the laboratory. The tests replicated standard impulse waves and were conducted in stages at 20 kV, 30 kV, 40 kV, and 50 kV levels, with each level repeated several times for data reliability. The main parameters analyzed included the measured peak voltage, response time (μs), and the cutting percentage compared to unprotected conditions, based on validated oscilloscope readings (time/div and volt/div). The results showed that both arresters reduced the induced voltage in most test scenarios, with the highest effectiveness occurring at 30 kV impulses. Quantitatively, ceramic arresters achieve a cutoff of 0.39–4.17 V (2.27–22.3%), while polymer arresters achieve 1.46–4.67 V (8.44–24.97%), and at 20 kV no significant cutoff is observed. In general, the performance of polymer lighting arresters is better than ceramic lighting arresters, which indicates the ability of polymer materials and housing designs to maintain lower residual voltages when facing fast transients
Abstrak
Gangguan petir seringkali menimbulkan tegangan lebih terinduksi pada saluran udara distribusi tegangan menengah 20 kV yang berakibat memperpendek umur peralatan dan memicu pemadaman listrik. Penelitian ini bertujuan mengevaluasi kinerja pemotongan dua tipe lightning arrester berbahan keramik dan berbahan polimer dalam mereduksi lonjakan tegangan akibat induksi petir melalui pengujian impuls tegangan tinggi di laboratorium. Pengujian mereplikasi gelombang impuls standar dan dilakukan bertingkat pada level 20 kV, 30 kV, 40 kV, dan 50 kV dimana setiap level diulang beberapa kali untuk reliabilitas data. Parameter utama yang dianalisis meliputi tegangan puncak terukur, respons waktu (μs), serta persentase pemotongan terhadap kondisi tanpa proteksi, berdasarkan pembacaan osiloskop yang telah divalidasi (time/div dan volt/div). Hasil menunjukkan kedua arrester menurunkan tegangan induksi pada sebagian besar skenario uji, dengan efektivitas tertinggi muncul pada impuls 30 kV. Secara kuantitatif, arrester keramik mencapai pemotongan 0,39–4,17 V (2,27–22,3%), sedangkan arrester polimer 1,46–4,67 V (8,44–24,97%) dan pada tegangan 20 kV tidak teramati pemotongan berarti. Secara umum kinerja lighting arrester polimer lebih baik dibandingkan lighting arrester berbahan keramik, yang mengindikasikan kemampuan material dan rancangan housing polimer untuk menjaga tegangan residual lebih rendah saat menghadapi transien cepat
Universitas Tarumanagara
Title: PERFORMANCE STUDY OF OVERVOLTAGE CUTTING BY LIGHTNING ARRESTER DUE TO LIGHTNING INDUCTION
Description:
Lightning disturbances often cause induced overvoltages on 20 kV medium voltage distribution overhead lines, which can shorten equipment life and trigger power outages.
This study aims to evaluate the cutting performance of two types of lightning arresters made of ceramic and polymer in reducing lightning-induced voltage surges through high-voltage impulse testing in the laboratory.
The tests replicated standard impulse waves and were conducted in stages at 20 kV, 30 kV, 40 kV, and 50 kV levels, with each level repeated several times for data reliability.
The main parameters analyzed included the measured peak voltage, response time (μs), and the cutting percentage compared to unprotected conditions, based on validated oscilloscope readings (time/div and volt/div).
The results showed that both arresters reduced the induced voltage in most test scenarios, with the highest effectiveness occurring at 30 kV impulses.
Quantitatively, ceramic arresters achieve a cutoff of 0.
39–4.
17 V (2.
27–22.
3%), while polymer arresters achieve 1.
46–4.
67 V (8.
44–24.
97%), and at 20 kV no significant cutoff is observed.
In general, the performance of polymer lighting arresters is better than ceramic lighting arresters, which indicates the ability of polymer materials and housing designs to maintain lower residual voltages when facing fast transients
Abstrak
Gangguan petir seringkali menimbulkan tegangan lebih terinduksi pada saluran udara distribusi tegangan menengah 20 kV yang berakibat memperpendek umur peralatan dan memicu pemadaman listrik.
Penelitian ini bertujuan mengevaluasi kinerja pemotongan dua tipe lightning arrester berbahan keramik dan berbahan polimer dalam mereduksi lonjakan tegangan akibat induksi petir melalui pengujian impuls tegangan tinggi di laboratorium.
Pengujian mereplikasi gelombang impuls standar dan dilakukan bertingkat pada level 20 kV, 30 kV, 40 kV, dan 50 kV dimana setiap level diulang beberapa kali untuk reliabilitas data.
Parameter utama yang dianalisis meliputi tegangan puncak terukur, respons waktu (μs), serta persentase pemotongan terhadap kondisi tanpa proteksi, berdasarkan pembacaan osiloskop yang telah divalidasi (time/div dan volt/div).
Hasil menunjukkan kedua arrester menurunkan tegangan induksi pada sebagian besar skenario uji, dengan efektivitas tertinggi muncul pada impuls 30 kV.
Secara kuantitatif, arrester keramik mencapai pemotongan 0,39–4,17 V (2,27–22,3%), sedangkan arrester polimer 1,46–4,67 V (8,44–24,97%) dan pada tegangan 20 kV tidak teramati pemotongan berarti.
Secara umum kinerja lighting arrester polimer lebih baik dibandingkan lighting arrester berbahan keramik, yang mengindikasikan kemampuan material dan rancangan housing polimer untuk menjaga tegangan residual lebih rendah saat menghadapi transien cepat.
Related Results
Localizaciones con impactos de rayos recurrentes : aportación a la distribución geográfica de rayos con corrientes extremas y a la caracterización de rayos que afectan aerogeneradores
Localizaciones con impactos de rayos recurrentes : aportación a la distribución geográfica de rayos con corrientes extremas y a la caracterización de rayos que afectan aerogeneradores
(English) Nowadays, lightning presents a challenge to the proper functioning of an increasingly complex electrical system. One of the most sensitive and exposed to lightning elemen...
PENGUJIAN DALAM PENGGUNAAN DAN DIAGNOSIS ARRESTER METAL OXIDE TANPA CELAH
PENGUJIAN DALAM PENGGUNAAN DAN DIAGNOSIS ARRESTER METAL OXIDE TANPA CELAH
This paper describes the testing strategies and risk assessment services for use in the diagnosis of metal oxide arrester without gaps that are installed substations. Different cas...
Analisis Arrester Sebagai Sistem Proteksi Pada Transformator di Gardu Induk Keramasan
Analisis Arrester Sebagai Sistem Proteksi Pada Transformator di Gardu Induk Keramasan
Lightning overvoltage is a periodic overvoltage caused by external causes. An arrester is equipment that protects installations from overvoltage disturbances due to lightning strik...
Radio pulse power distribution of lightning in Jupiter's 2021-2022 stealth superstorms
Radio pulse power distribution of lightning in Jupiter's 2021-2022 stealth superstorms
OverviewJovian lightning has been investigated by every spacecraft mission that visited Jupiter prior to Juno. Lightning is valued because it traces locations with active moist con...
supriyatna ANALISIS KOORDINASI ISOLASI DI GARDU INDUK KUTA TERHADAP TEGANGAN LEBIH AKIBAT SAMBARAN PETIR PADA SALURAN TRANSMISI 150 KV (Pak Supriyatna)
supriyatna ANALISIS KOORDINASI ISOLASI DI GARDU INDUK KUTA TERHADAP TEGANGAN LEBIH AKIBAT SAMBARAN PETIR PADA SALURAN TRANSMISI 150 KV (Pak Supriyatna)
Sambaran petir pada saluran transmisi 150 kV dapat menimbulkan tegangan lebih yang akan membahayakan peralatan jika tegangan tersebut melampaui tingkat isolasi dasar peralatan (TID...
Analisa Karakteristik Arrester pada Gardu Distribusi 20 kV ST 350 Penyulang Merpati
Analisa Karakteristik Arrester pada Gardu Distribusi 20 kV ST 350 Penyulang Merpati
Arrester salah satu peralatan pada sistem tenaga listrk yang dapat melindungi peralatan listrik dari gangguan eksternal yang diakibatkan oleh tegangan lebih surja petir. Analisa ...
Long-range Lightning Interferometry (A Simulation Study)
Long-range Lightning Interferometry (A Simulation Study)
Traditional long-range lightning detection and location networks use Time-of-Arrival (TOA) differences, and a single timestamp to locate lightning events. For long propagation dist...
Pemodelan Tegangan Lebih Disebabkan Sambaran Petir Menggunakan Arrester IEEE Dengan Aplikasi ATP-EMTP Pada Studi Kasus Di Nias
Pemodelan Tegangan Lebih Disebabkan Sambaran Petir Menggunakan Arrester IEEE Dengan Aplikasi ATP-EMTP Pada Studi Kasus Di Nias
Lightning has always been a dangerous threat to the equipment of electric power systems consisting of: power plants, substations, transmission lines and distribution lines. General...