Development of Prototype Valve to Separate Two-Phase Air-Water Flows

View through CrossRef
A certain nuclear power plant uses a siphon to bring cooling water into the plant during emergency operations. This siphon was “hardened” by adding a nuclear grade vacuum system to the siphon high points. A float valve, sized for the required air flow rate, was used to prevent water carryover into the vacuum system. In order to pass the required flow rate, the valve’s orifice size would be the largest produced by any manufacturer to date. Initial system testing revealed that the valve was not fully opening due to the high vacuum and the design of the valve opening mechanism. Analysis and testing developed a solution to the opening problem. However, a new problem was introduced — excessive liquid carryover. The liquid carryover rate was estimated at 6 gallons per minute. The liquid carryover was postulated to be due to droplet entrainment as high velocity air bubbles entered the valve body, ruptured the air-water interface, and carried some of the resultant droplets through the valve outlet as the valve opened due to falling water level. Additionally, valve operating mechanism changes resulted in it responding slower. Using information learned from modifying the original valve, a new valve design was conceived that would be based on the following 3 principles: 1) liquid momentum must cause it to separate from the air upon entrance into the valve body; 2) enough distance and space must exist inside the body to allow gravity to act upon any liquid droplets to allow them to fall back into the liquid pool instead of being carried out of the valve toward the vacuum system; 3) valve operating mechanism must respond quickly enough to close the valve upon rapid liquid influx. The valve manufacturer reviewed the conceptual design and produced a prototype. The prototype valve was successfully tested with zero water carryover plus better flow versus pressure loss performance than the original valve. The valve also functioned acceptably during shaker table testing to simulate earthquake conditions.
Title: Development of Prototype Valve to Separate Two-Phase Air-Water Flows
Description:
A certain nuclear power plant uses a siphon to bring cooling water into the plant during emergency operations.
This siphon was “hardened” by adding a nuclear grade vacuum system to the siphon high points.
A float valve, sized for the required air flow rate, was used to prevent water carryover into the vacuum system.
In order to pass the required flow rate, the valve’s orifice size would be the largest produced by any manufacturer to date.
Initial system testing revealed that the valve was not fully opening due to the high vacuum and the design of the valve opening mechanism.
Analysis and testing developed a solution to the opening problem.
However, a new problem was introduced — excessive liquid carryover.
The liquid carryover rate was estimated at 6 gallons per minute.
The liquid carryover was postulated to be due to droplet entrainment as high velocity air bubbles entered the valve body, ruptured the air-water interface, and carried some of the resultant droplets through the valve outlet as the valve opened due to falling water level.
Additionally, valve operating mechanism changes resulted in it responding slower.
Using information learned from modifying the original valve, a new valve design was conceived that would be based on the following 3 principles: 1) liquid momentum must cause it to separate from the air upon entrance into the valve body; 2) enough distance and space must exist inside the body to allow gravity to act upon any liquid droplets to allow them to fall back into the liquid pool instead of being carried out of the valve toward the vacuum system; 3) valve operating mechanism must respond quickly enough to close the valve upon rapid liquid influx.
The valve manufacturer reviewed the conceptual design and produced a prototype.
The prototype valve was successfully tested with zero water carryover plus better flow versus pressure loss performance than the original valve.
The valve also functioned acceptably during shaker table testing to simulate earthquake conditions.

Related Results

An Acoustically Controlled Down-Hole Safety Valve (SCSSSV)
An Acoustically Controlled Down-Hole Safety Valve (SCSSSV)
American Institute of Mining, Metallurgical, and Petroleum Engineers, Inc. Abstract A surface-controlled subsurface safety valve...
Comparison of Heart Valve Circumference Examined Before and After 10% Formalin Fixation
Comparison of Heart Valve Circumference Examined Before and After 10% Formalin Fixation
Objective: To compare the heart valve circumference before and after 10% formalin fixation. Materials and Methods: The study analyzed 63 Thai human cadaveric hearts. Each heart val...
Reciprocating compressor valve damage estimation under varying speeds through the acoustic emission technique
Reciprocating compressor valve damage estimation under varying speeds through the acoustic emission technique
Purpose The purpose of this paper is to examine the effect of reciprocating compressor speeds and valve conditions on the roor-mean-square (RMS) value of burst acoustic emission (A...
Modeling and simulation analysis of a novel proportional water flow valve with a digital pilot stage
Modeling and simulation analysis of a novel proportional water flow valve with a digital pilot stage
The position straightness of the hydraulic supports is the key factor to the intelligent fully mechanized mining, and the adjacent cylinder is the actuator used to pull the hydraul...
Environmental Surveillance Protocols for Highly Pathogenic Avian Influenza (HPAI) v2
Environmental Surveillance Protocols for Highly Pathogenic Avian Influenza (HPAI) v2
EnvironmentalSurveillance Protocols for Highly Pathogenic Avian Influenza (HPAI) This comprehensive protocol suite enables systematic environmental surveillance for avian influenza...

Back to Top