Characteristics of Various Single Wind-Power Distributed Generation Placements for Voltage Drop Improvement in a 22 kV Distribution System

View through CrossRef
A major challenge in distribution systems is the issue of voltage drop along the distribution line resulting from an increased load capacity connected to the utility. A significant voltage drop can affect the performance of a distribution system and cause quality issues for end users, impacting the system’s long-term sustainability and reliability. Therefore, regulations have been set stating that the voltage level should not be more that 5% higher or lower than the rated voltage. Thus, in this study, we aimed to evaluate the voltage level characteristics of a 22 kV distribution system that replicates the actual distribution system in the Provincial Electricity Authority. A voltage improvement technique based on distributed generation placement was proposed. In addition, the distribution system characteristics with and without distributed generation placement were evaluated under fault conditions. The results indicate that distributed generation placement in the distribution system can improve the voltage level along the distribution line. However, the level of increase in voltage depends on the size of the load, the capacity of the distributed generation, and the location of the distributed generation system on the distribution line. Furthermore, placing a distributed generation system with a minimum capacity at the proposed location can improve the voltage within the utility’s standard level. Thus, the installation of a distributed generation system in the distribution system is beneficial in terms of voltage improvement in the distribution system and provides the power system with a sustainable method to address the issue of voltage drop.
Title: Characteristics of Various Single Wind-Power Distributed Generation Placements for Voltage Drop Improvement in a 22 kV Distribution System
Description:
A major challenge in distribution systems is the issue of voltage drop along the distribution line resulting from an increased load capacity connected to the utility.
A significant voltage drop can affect the performance of a distribution system and cause quality issues for end users, impacting the system’s long-term sustainability and reliability.
Therefore, regulations have been set stating that the voltage level should not be more that 5% higher or lower than the rated voltage.
Thus, in this study, we aimed to evaluate the voltage level characteristics of a 22 kV distribution system that replicates the actual distribution system in the Provincial Electricity Authority.
A voltage improvement technique based on distributed generation placement was proposed.
In addition, the distribution system characteristics with and without distributed generation placement were evaluated under fault conditions.
The results indicate that distributed generation placement in the distribution system can improve the voltage level along the distribution line.
However, the level of increase in voltage depends on the size of the load, the capacity of the distributed generation, and the location of the distributed generation system on the distribution line.
Furthermore, placing a distributed generation system with a minimum capacity at the proposed location can improve the voltage within the utility’s standard level.
Thus, the installation of a distributed generation system in the distribution system is beneficial in terms of voltage improvement in the distribution system and provides the power system with a sustainable method to address the issue of voltage drop.

Related Results

Modelado de un Recuperador Dinámico de Tensión para el Mejoramiento de la Calidad de la Onda de Tensión
Modelado de un Recuperador Dinámico de Tensión para el Mejoramiento de la Calidad de la Onda de Tensión
[1]          R. C. Dugan, H. W. Beaty, y S. Santoso, Electrical Power Systems Quality, Third edition. Tata McGraw Hill Education, 2012.[2]          J. Arrilaga y N. R. Watson, Powe...
Wind lidars within Dutch offshore wind farms
Wind lidars within Dutch offshore wind farms
The growing number of wind farms in the Dutch part of the North Sea [1] offers the necessity, as well as the opportunity, to measure the meteorological conditions at these location...
Savonius Rotor for Offshore Wind Energy Conversion
Savonius Rotor for Offshore Wind Energy Conversion
Abstract Analysis of performance is presented for wind energy conversion by a Savonius type vertical axis rotor configured for generation of electrical power. The...
Analysis of Senegal Type Vertical Axis Wind Turbines Arrangement in Wind Farm
Analysis of Senegal Type Vertical Axis Wind Turbines Arrangement in Wind Farm
Background: In a wind farm, the wind speed of the downstream wind turbine will be lower than the wind speed of the upstream wind turbine due to the influence of the wake. Therefore...
Multiterminal HVDC transmissions systems for offshore wind
Multiterminal HVDC transmissions systems for offshore wind
Offshore wind is emerging as one of the future energy vectors. Offshore wind power plants locations provide more strong and constant wind speed that allows to extract more power co...
Stability Modeling and Analysis of Grid Connected Doubly Fed Wind Energy Generation Based on Small Signal Model
Stability Modeling and Analysis of Grid Connected Doubly Fed Wind Energy Generation Based on Small Signal Model
Stable wind power generation can ensure the quality of power transmitted by the grid. The application of large-scale grid-connected wind power systems will induce problems such as ...
Modeling of the dynamics of wind to power conversion including high wind speed behavior
Modeling of the dynamics of wind to power conversion including high wind speed behavior
AbstractThis paper proposes and validates an efficient, generic and computationally simple dynamic model for the conversion of the wind speed at hub height into the electrical powe...
Solar wind interaction with comet 67P around perihelion
Solar wind interaction with comet 67P around perihelion
AbstractNear perihelion, when comet 67P was most active, the Rosetta spacecraft resided inside the comet induced magnetosphere. The solar wind magnetic field was still present, but...

Back to Top