A Hybrid Flexible Neutral Grounding Mode for Large Generators
View through CrossRef
Single-phase ground faults frequently occur at the generator stator windings. To realize reliable arc suppression, a dual-frequency active arc-suppression strategy has been widely considered. However, the existing method needs an inverter with large capacity, which is large in volume and high in cost, causing limited engineering application prospects. To reduce the capacity, a novel hybrid flexible neutral grounding method for large generators is proposed in this paper. It combines the dual-frequency active arc-suppression strategy with the arc-suppression coil-grounding mode. Thus, most of the fundamental components in the fault current are compensated by the arc-suppression coil, and the rest are compensated by the active arc-suppression device. The capacity of the inverter can be greatly reduced under the premise of reliably realizing arc suppression. To identify transient and permanent ground faults after arc suppression, the phase-angle relation between the third-harmonic voltage and current variation at the generator neutral point is used to form the fault-type identification criterion. The third-harmonic quantities can avoid the blind area at the neutral point caused by fundamental quantities. Simulation and experimental test results verify the effectiveness of the proposed method.
Title: A Hybrid Flexible Neutral Grounding Mode for Large Generators
Description:
Single-phase ground faults frequently occur at the generator stator windings.
To realize reliable arc suppression, a dual-frequency active arc-suppression strategy has been widely considered.
However, the existing method needs an inverter with large capacity, which is large in volume and high in cost, causing limited engineering application prospects.
To reduce the capacity, a novel hybrid flexible neutral grounding method for large generators is proposed in this paper.
It combines the dual-frequency active arc-suppression strategy with the arc-suppression coil-grounding mode.
Thus, most of the fundamental components in the fault current are compensated by the arc-suppression coil, and the rest are compensated by the active arc-suppression device.
The capacity of the inverter can be greatly reduced under the premise of reliably realizing arc suppression.
To identify transient and permanent ground faults after arc suppression, the phase-angle relation between the third-harmonic voltage and current variation at the generator neutral point is used to form the fault-type identification criterion.
The third-harmonic quantities can avoid the blind area at the neutral point caused by fundamental quantities.
Simulation and experimental test results verify the effectiveness of the proposed method.
Related Results
Performance Analysis and Optimization Designs for HVDC Grounding Electrodes
Performance Analysis and Optimization Designs for HVDC Grounding Electrodes
High voltage direct current(HVDC) grounding electrodes can provide a current-leakage channel for ground faults, ensuring HVDC systems’ safety and reliability. The HVDC grounding el...
Grounding of the mobile radio nodes in soils with vertical differential electrophysical causes
Grounding of the mobile radio nodes in soils with vertical differential electrophysical causes
When using overestimated values of soil parameters, the calculated resistance of the grounding electrodes will be increased and a larger number of electrodes will be required. This...
Distribution Network Voltage Arc Suppression Method Based on Flexible Regulation of Neutral Point Potential of the New Grounding Transformer
Distribution Network Voltage Arc Suppression Method Based on Flexible Regulation of Neutral Point Potential of the New Grounding Transformer
Aiming at the problems that the existing arc suppression cabinet technology cannot adjust the zero sequence voltage flexibly and the control and hardware implementation of active a...
PENGARUH KELEMBABAN TANAH TERHADAP TAHANAN PENTANAHAN STUDI KASUS PADA GARDU INDUK KEMAYORAN 150 kV
PENGARUH KELEMBABAN TANAH TERHADAP TAHANAN PENTANAHAN STUDI KASUS PADA GARDU INDUK KEMAYORAN 150 kV
Abstract
The value of grounding resistance at the substation should be 0 Ω or less than 1 Ω. The value of grounding resistance is influenced by the resistivity and the ground...
Grounding Performance of Hydrogel, Silica Gel and Charcoal Ash as Additive Material in Grounding System
Grounding Performance of Hydrogel, Silica Gel and Charcoal Ash as Additive Material in Grounding System
Grounding enhancement materials (GEMs) are one of the additive materials which can change the grounding performance without lots of significant costs. The study aimed to assess the...
Stability and dynamics of geophysical neutral vortices
Stability and dynamics of geophysical neutral vortices
(English) Mesoscale and submesoscale vortical structures are ubiquitous in the ocean and atmosphere. Most of these vortices are long-lived with a lifetime of several months. They o...
Research on Performance of Grounding Conductor Based on Multi-Physics
Research on Performance of Grounding Conductor Based on Multi-Physics
Abstract
The performance analysis of the grounding conductor is of great significance for improving the design and construction level of the grounding grid and ratio...
AMPLITUDE METHODS FOR CONTROL OF GAS GENERATORS WATER SAVING SYSTEMS
AMPLITUDE METHODS FOR CONTROL OF GAS GENERATORS WATER SAVING SYSTEMS
The methods of control of the technical station of gas generators of systems for saving and supplying water are examined, which are based on the variation of their amplitude-freque...