Study on Shock Disinfection in a Fire Extinguishing Water Supply System

View through CrossRef
The biofilms generated in a fire extinguishing water supply system can cause corrosion and a reduction in the water supply capacity; thus, degrading the system performance. To mitigate microbial corrosion, appropriate disinfection measures are necessary. In this study, the secondary addition of chlorine is employed to investigate the kinetics of chlorine decay, and shock disinfection is applied to investigate the removal efficiency of corrosion bacteria, and the microbial composition of a biofilm on the pipe wall was also clarified. The results show that the residual chlorine content in the secondary chlorination process was directly correlated with the decay rate of residual chlorine and the corrosion rate of the pipe wall. Additionally, the chlorine impact disinfection method could reduce the electrochemical corrosion phenomenon of the pipe wall. When the concentration of chlorine was 3 mg/L, the removal rate of corrosion bacteria was higher in 60 min than in 30 min. Specifically, most of the bacteria were inactivated in 60 min and the biofilm was severely damaged. Shock disinfection could significantly inactivate all microflora in the biofilm; the relative abundances of microflora varied significantly, while the change of microflora at the phylum level was insignificant. This study can provide theoretical support for the secondary addition of chlorine and shock disinfection in a fire extinguishing water supply system.
Title: Study on Shock Disinfection in a Fire Extinguishing Water Supply System
Description:
The biofilms generated in a fire extinguishing water supply system can cause corrosion and a reduction in the water supply capacity; thus, degrading the system performance.
To mitigate microbial corrosion, appropriate disinfection measures are necessary.
In this study, the secondary addition of chlorine is employed to investigate the kinetics of chlorine decay, and shock disinfection is applied to investigate the removal efficiency of corrosion bacteria, and the microbial composition of a biofilm on the pipe wall was also clarified.
The results show that the residual chlorine content in the secondary chlorination process was directly correlated with the decay rate of residual chlorine and the corrosion rate of the pipe wall.
Additionally, the chlorine impact disinfection method could reduce the electrochemical corrosion phenomenon of the pipe wall.
When the concentration of chlorine was 3 mg/L, the removal rate of corrosion bacteria was higher in 60 min than in 30 min.
Specifically, most of the bacteria were inactivated in 60 min and the biofilm was severely damaged.
Shock disinfection could significantly inactivate all microflora in the biofilm; the relative abundances of microflora varied significantly, while the change of microflora at the phylum level was insignificant.
This study can provide theoretical support for the secondary addition of chlorine and shock disinfection in a fire extinguishing water supply system.

Related Results

Automated control methodology of fire extinguishing means scientific substantiation
Automated control methodology of fire extinguishing means scientific substantiation
The issue of firefighters territorial dispersal along the perimeter of a forest fire during its extinguishing is considered. Justification of firefighters’ coordination actions in ...
Condensed Aerosol Generators in Fire Safety of Buildings. Part 2 – Selected Issues Related to Design, Installation and Maintenance
Condensed Aerosol Generators in Fire Safety of Buildings. Part 2 – Selected Issues Related to Design, Installation and Maintenance
Aim: The purpose of this paper is to review selected requirements for the design, installation, and maintenance of fixed fire extinguishing systems based on condensed aerosol gener...
Integrated hydrological modelling for sustainable water allocation planning : Mkomazi Basin, South Africa case study
Integrated hydrological modelling for sustainable water allocation planning : Mkomazi Basin, South Africa case study
Allocation of freshwater resources between societal needs and natural ecological systems is of great concern for water managers. This development has challenged decision-makers reg...
Generation and modulation of shock waves in two-dimensional polariton condensates
Generation and modulation of shock waves in two-dimensional polariton condensates
Due to the ability of exciton-polariton condensates formed in semiconductor microcavities to be achieved at room temperature and their characteristics such as non-equilibrium and s...
WEAP-MODFLOW dynamic modeling approach to evaluate surface water and groundwater supply sources of Addis Ababa city
WEAP-MODFLOW dynamic modeling approach to evaluate surface water and groundwater supply sources of Addis Ababa city
The integration between WEAP and MODFLOW models coupled via LinkKitchen helps to create a dynamic link between surface water and groundwater supply sources of Addis Ababa city. Pos...

Back to Top