ANALISIS KINERJA CHILLER DI GEDUNG SENAYAN CITY

View through CrossRef
Abstract. Research conducted in the building Senayan City in June 2016 using qualitative research methods. Standards are used as a benchmark the performance of each chiller uses ISO 6390 in 2011 on Energy Conservation Air system administration Building. These aspects are analyzed to determine the performance of the chiller is the temperature of chilled water, flow chilled water and compressor power. As for the influence of the three aspects is the temperature of the outside environment. By calculating the cooling capacity, the highest Coefficient of Permonace (COP) value can be determined each chiller.Chiller performance analysis results obtained COP value of the highest attainable number 1 at 7.31 chiller, chiller number 2 at 8.03 and chiller number 3 6:27. These values ​​meet the mi nimum value of COP according to ISO standards. Lowest chiller COP value number 1 by 5.08, number 2 for 5.12 chiller and chiller number 3 at 4.22. Third party chiller COP minimum value does not meet the minimum standards of the COP. Chiller number 3 has the lowest minimum number COP and far below the minimum stadar.Judging from the value of cooling capacity and COP, chiller performance is not good enough is the number 3. And the chiller that has good enough performance is number 1 and 2 Abstrak Penelitian ini bertujuan untuk menghasilkan data analisis kinerja chiller di gedung Senayan City. Penelitian yang dilakukan di gedung Senayan City pada bulan Juni 2016 ini menggunakan metode penelitian kualitatif. Standar yang digunakan sebagai patokan kinerja masing-masing chiller menggunakan SNI 6390 tahun 2011 tentang Konservasi Energi Sistem Tata Udara Bangunan Gedung. Aspek-aspek yang dianalisis untuk mengetahui kinerja chiller adalah temperatur chilled water, flow chilled water dan power kompresor. Adapun yang mempengaruhi ketiga aspek tersebut adalah temperatur lingkungan luar. Dengan menghitung kapasitas pendinginan, dapat ditentukan nilai Coefficient of Permonace (COP) tertinggi masing-masing chiller. Hasil analisis kinerja chiller didapat Nilai COP tertinggi yang dapat dicapai chiller nomor 1 sebesar 7,31, chiller nomor 2 sebesar 8,03 dan chiller nomor 3 6.27. Ketiga nilai tersebut memenuhi nilai minimum standar COP menurut SNI. Nilai COP terendah  chiller nomor 1 sebesar 5,08, chiller nomor 2 sebesar 5,12 dan chiller nomor 3 sebesar 4,22. Ketiga nilai minimum COP ketiga chiller ini tidak memenuhi standar minimum COP. Chiller nomor 3 mempunyai angka minimum COP paling rendah dan jauh dibawah stadar minimum. Dilihat dari kapasitas pendinginan dan nilai COP, chiller yang kinerja kurang baik adalah chiller nomor 3. Dan chiller yang performanya cukup baik adalah chiller nomor 1 dan 2.
Title: ANALISIS KINERJA CHILLER DI GEDUNG SENAYAN CITY
Description:
Abstract.
Research conducted in the building Senayan City in June 2016 using qualitative research methods.
Standards are used as a benchmark the performance of each chiller uses ISO 6390 in 2011 on Energy Conservation Air system administration Building.
These aspects are analyzed to determine the performance of the chiller is the temperature of chilled water, flow chilled water and compressor power.
As for the influence of the three aspects is the temperature of the outside environment.
By calculating the cooling capacity, the highest Coefficient of Permonace (COP) value can be determined each chiller.
Chiller performance analysis results obtained COP value of the highest attainable number 1 at 7.
31 chiller, chiller number 2 at 8.
03 and chiller number 3 6:27.
These values ​​meet the mi nimum value of COP according to ISO standards.
Lowest chiller COP value number 1 by 5.
08, number 2 for 5.
12 chiller and chiller number 3 at 4.
22.
Third party chiller COP minimum value does not meet the minimum standards of the COP.
Chiller number 3 has the lowest minimum number COP and far below the minimum stadar.
Judging from the value of cooling capacity and COP, chiller performance is not good enough is the number 3.
And the chiller that has good enough performance is number 1 and 2 Abstrak Penelitian ini bertujuan untuk menghasilkan data analisis kinerja chiller di gedung Senayan City.
Penelitian yang dilakukan di gedung Senayan City pada bulan Juni 2016 ini menggunakan metode penelitian kualitatif.
Standar yang digunakan sebagai patokan kinerja masing-masing chiller menggunakan SNI 6390 tahun 2011 tentang Konservasi Energi Sistem Tata Udara Bangunan Gedung.
Aspek-aspek yang dianalisis untuk mengetahui kinerja chiller adalah temperatur chilled water, flow chilled water dan power kompresor.
Adapun yang mempengaruhi ketiga aspek tersebut adalah temperatur lingkungan luar.
Dengan menghitung kapasitas pendinginan, dapat ditentukan nilai Coefficient of Permonace (COP) tertinggi masing-masing chiller.
Hasil analisis kinerja chiller didapat Nilai COP tertinggi yang dapat dicapai chiller nomor 1 sebesar 7,31, chiller nomor 2 sebesar 8,03 dan chiller nomor 3 6.
27.
Ketiga nilai tersebut memenuhi nilai minimum standar COP menurut SNI.
Nilai COP terendah  chiller nomor 1 sebesar 5,08, chiller nomor 2 sebesar 5,12 dan chiller nomor 3 sebesar 4,22.
Ketiga nilai minimum COP ketiga chiller ini tidak memenuhi standar minimum COP.
Chiller nomor 3 mempunyai angka minimum COP paling rendah dan jauh dibawah stadar minimum.
Dilihat dari kapasitas pendinginan dan nilai COP, chiller yang kinerja kurang baik adalah chiller nomor 3.
Dan chiller yang performanya cukup baik adalah chiller nomor 1 dan 2.

Related Results

PERBANDINGAN KELAYAKAN FINANSIAL GEDUNG GREEN BUILDING DAN NON- GREEN BUILDING MENGGUNAKAN METODE MONTE CARLO
PERBANDINGAN KELAYAKAN FINANSIAL GEDUNG GREEN BUILDING DAN NON- GREEN BUILDING MENGGUNAKAN METODE MONTE CARLO
Since 2011, Indonesia has been committed to reducing greenhouse gas emissions, one of which is by implementing green buildings in office buildings. The aim of implementing green bu...
IDENTIFIKASI DAN KLASIFIKASI ASET INFRASTRUKTUR BANGUNAN GEDUNG DI UNIVERSITAS PALANGKA RAYA
IDENTIFIKASI DAN KLASIFIKASI ASET INFRASTRUKTUR BANGUNAN GEDUNG DI UNIVERSITAS PALANGKA RAYA
Aset infrastruktur bangunan gedung di lingkungan kampus berperan penting sebagai sarana penunjang kegiatan akademik maupun non akademik. Universitas Palangka Raya sebagai penyeleng...
Analisis Chiller Dengan Menggunaan R123 Dan R134a Pada Kinerja Pendinginan
Analisis Chiller Dengan Menggunaan R123 Dan R134a Pada Kinerja Pendinginan
AbstrakChiller adalah mesin refrigerasi yang memiliki fungsi utama mendinginkan air pada sisi evaporator, air yang didinginkan selanjutnya didistribusi ke alat penukar kalor (FCU; ...
Studi Analisis Beban Dorong untuk Gedung Beton Bertulang
Studi Analisis Beban Dorong untuk Gedung Beton Bertulang
Perencanaan struktur bangunan gedung tahan gempa di negara Indonesia menjadi suatu hal yang sangat penting mengingat sebagian besar wilayah Indonesia terletak dalam wilayah gempa d...
ANALISIS PENGGUNAAN SENAYAN LIBRARY MANAGEMENT SYSTEM (SLIMS) DI PERPUSTAKAAN MAN 1 PADANGSIDIMPUAN PLUS RISET
ANALISIS PENGGUNAAN SENAYAN LIBRARY MANAGEMENT SYSTEM (SLIMS) DI PERPUSTAKAAN MAN 1 PADANGSIDIMPUAN PLUS RISET
Penelitian ini bertujuan untuk menganalisis (1) penggunaan Senayan Library Management System (SLIMS) pada siswa di MAN 1 Padangsidimpuan Plus Riset (2) penggunaan Senayan Library M...
Analyzing the efficiency of moderate and deep cooling of air at the inlet of gas turbine in various climatic conditions
Analyzing the efficiency of moderate and deep cooling of air at the inlet of gas turbine in various climatic conditions
The efficiency of deep cooling air at the inlet of gas turbine unite to the temperature of 10 °С by waste heat recovery combined absorption-ejector chiller was analyzed in climatic...
ANALISIS PEMELIHARAAN BANGUNAN GEDUNG (STUDI KASUS: THE ROYAL IDI HOTEL)
ANALISIS PEMELIHARAAN BANGUNAN GEDUNG (STUDI KASUS: THE ROYAL IDI HOTEL)
Pemeliharaan bangunan gedung merupakan kegiatan yang sangat penting dilakukan dimana pemeliharaan dapat meningkatkan umur pakai dari bangunan tesebut. Di Indonesia peraturan tentan...

Back to Top