ANALISIS KINERJA CHILLER DI GEDUNG SENAYAN CITY

View through CrossRef
Abstract. Research conducted in the building Senayan City in June 2016 using qualitative research methods. Standards are used as a benchmark the performance of each chiller uses ISO 6390 in 2011 on Energy Conservation Air system administration Building. These aspects are analyzed to determine the performance of the chiller is the temperature of chilled water, flow chilled water and compressor power. As for the influence of the three aspects is the temperature of the outside environment. By calculating the cooling capacity, the highest Coefficient of Permonace (COP) value can be determined each chiller.Chiller performance analysis results obtained COP value of the highest attainable number 1 at 7.31 chiller, chiller number 2 at 8.03 and chiller number 3 6:27. These values ​​meet the mi nimum value of COP according to ISO standards. Lowest chiller COP value number 1 by 5.08, number 2 for 5.12 chiller and chiller number 3 at 4.22. Third party chiller COP minimum value does not meet the minimum standards of the COP. Chiller number 3 has the lowest minimum number COP and far below the minimum stadar.Judging from the value of cooling capacity and COP, chiller performance is not good enough is the number 3. And the chiller that has good enough performance is number 1 and 2 Abstrak Penelitian ini bertujuan untuk menghasilkan data analisis kinerja chiller di gedung Senayan City. Penelitian yang dilakukan di gedung Senayan City pada bulan Juni 2016 ini menggunakan metode penelitian kualitatif. Standar yang digunakan sebagai patokan kinerja masing-masing chiller menggunakan SNI 6390 tahun 2011 tentang Konservasi Energi Sistem Tata Udara Bangunan Gedung. Aspek-aspek yang dianalisis untuk mengetahui kinerja chiller adalah temperatur chilled water, flow chilled water dan power kompresor. Adapun yang mempengaruhi ketiga aspek tersebut adalah temperatur lingkungan luar. Dengan menghitung kapasitas pendinginan, dapat ditentukan nilai Coefficient of Permonace (COP) tertinggi masing-masing chiller. Hasil analisis kinerja chiller didapat Nilai COP tertinggi yang dapat dicapai chiller nomor 1 sebesar 7,31, chiller nomor 2 sebesar 8,03 dan chiller nomor 3 6.27. Ketiga nilai tersebut memenuhi nilai minimum standar COP menurut SNI. Nilai COP terendah  chiller nomor 1 sebesar 5,08, chiller nomor 2 sebesar 5,12 dan chiller nomor 3 sebesar 4,22. Ketiga nilai minimum COP ketiga chiller ini tidak memenuhi standar minimum COP. Chiller nomor 3 mempunyai angka minimum COP paling rendah dan jauh dibawah stadar minimum. Dilihat dari kapasitas pendinginan dan nilai COP, chiller yang kinerja kurang baik adalah chiller nomor 3. Dan chiller yang performanya cukup baik adalah chiller nomor 1 dan 2.
Title: ANALISIS KINERJA CHILLER DI GEDUNG SENAYAN CITY
Description:
Abstract.
Research conducted in the building Senayan City in June 2016 using qualitative research methods.
Standards are used as a benchmark the performance of each chiller uses ISO 6390 in 2011 on Energy Conservation Air system administration Building.
These aspects are analyzed to determine the performance of the chiller is the temperature of chilled water, flow chilled water and compressor power.
As for the influence of the three aspects is the temperature of the outside environment.
By calculating the cooling capacity, the highest Coefficient of Permonace (COP) value can be determined each chiller.
Chiller performance analysis results obtained COP value of the highest attainable number 1 at 7.
31 chiller, chiller number 2 at 8.
03 and chiller number 3 6:27.
These values ​​meet the mi nimum value of COP according to ISO standards.
Lowest chiller COP value number 1 by 5.
08, number 2 for 5.
12 chiller and chiller number 3 at 4.
22.
Third party chiller COP minimum value does not meet the minimum standards of the COP.
Chiller number 3 has the lowest minimum number COP and far below the minimum stadar.
Judging from the value of cooling capacity and COP, chiller performance is not good enough is the number 3.
And the chiller that has good enough performance is number 1 and 2 Abstrak Penelitian ini bertujuan untuk menghasilkan data analisis kinerja chiller di gedung Senayan City.
Penelitian yang dilakukan di gedung Senayan City pada bulan Juni 2016 ini menggunakan metode penelitian kualitatif.
Standar yang digunakan sebagai patokan kinerja masing-masing chiller menggunakan SNI 6390 tahun 2011 tentang Konservasi Energi Sistem Tata Udara Bangunan Gedung.
Aspek-aspek yang dianalisis untuk mengetahui kinerja chiller adalah temperatur chilled water, flow chilled water dan power kompresor.
Adapun yang mempengaruhi ketiga aspek tersebut adalah temperatur lingkungan luar.
Dengan menghitung kapasitas pendinginan, dapat ditentukan nilai Coefficient of Permonace (COP) tertinggi masing-masing chiller.
Hasil analisis kinerja chiller didapat Nilai COP tertinggi yang dapat dicapai chiller nomor 1 sebesar 7,31, chiller nomor 2 sebesar 8,03 dan chiller nomor 3 6.
27.
Ketiga nilai tersebut memenuhi nilai minimum standar COP menurut SNI.
Nilai COP terendah  chiller nomor 1 sebesar 5,08, chiller nomor 2 sebesar 5,12 dan chiller nomor 3 sebesar 4,22.
Ketiga nilai minimum COP ketiga chiller ini tidak memenuhi standar minimum COP.
Chiller nomor 3 mempunyai angka minimum COP paling rendah dan jauh dibawah stadar minimum.
Dilihat dari kapasitas pendinginan dan nilai COP, chiller yang kinerja kurang baik adalah chiller nomor 3.
Dan chiller yang performanya cukup baik adalah chiller nomor 1 dan 2.

Related Results

Analisis Chiller Dengan Menggunaan R123 Dan R134a Pada Kinerja Pendinginan
Analisis Chiller Dengan Menggunaan R123 Dan R134a Pada Kinerja Pendinginan
AbstrakChiller adalah mesin refrigerasi yang memiliki fungsi utama mendinginkan air pada sisi evaporator, air yang didinginkan selanjutnya didistribusi ke alat penukar kalor (FCU; ...
PENERAPAN E-KINERJA DI DINAS PERDAGANGAN KOTA SURAKARTA
PENERAPAN E-KINERJA DI DINAS PERDAGANGAN KOTA SURAKARTA
<p>Penelitan ini bertujuan untuk mengetahui penerapan sistem Elektronik-Kinerja (e-kinerja) di Dinas Perdagangan kota Surakarta serta untuk mengetahui kendala dan solusi dari...
Analyzing the efficiency of moderate and deep cooling of air at the inlet of gas turbine in various climatic conditions
Analyzing the efficiency of moderate and deep cooling of air at the inlet of gas turbine in various climatic conditions
The efficiency of deep cooling air at the inlet of gas turbine unite to the temperature of 10 °С by waste heat recovery combined absorption-ejector chiller was analyzed in climatic...
Kesesuaian Penerapan Prinsip Berjalan Kaki dan Bersepeda pada Kawasan TOD Istora Senayan Jakarta
Kesesuaian Penerapan Prinsip Berjalan Kaki dan Bersepeda pada Kawasan TOD Istora Senayan Jakarta
<p><span lang="IN">Jakarta memiliki kegiatan mobilitas yang tinggi dan sebagai upaya dalam memenuhi kebutuhan mobilitas masyarakat, pemerintah mulai menerapkan konsep T...
PERHITUNGAN KAPASITAS LIFT SEBAGAI SARANA TRANSPORTASI VERTIKAL PADA GEDUNG BERTINGKAT
PERHITUNGAN KAPASITAS LIFT SEBAGAI SARANA TRANSPORTASI VERTIKAL PADA GEDUNG BERTINGKAT
Pada Gedung 454 Politeknik Negeri Banyuwangi dengan tinggi 4 lantai pada gedung A dan C, tinggi 5 lantai pada gedung B masih menggunakan tangga sebagai alat transportasi vertikal u...
Pembuatan Aplikasi Sewa Gedung Wilayah Karawang Berbasis Android
Pembuatan Aplikasi Sewa Gedung Wilayah Karawang Berbasis Android
Berbagai kegiatan yang dihadiri banyak orang diperlukan tempat yang luas untuk dapat menampung banyak orang, tempat yang sering digunakan adalah gedung. Salah satu kegiatan yang se...

Back to Top