SHORT CIRCUIT FAULT ANALYSIS IN THE ELECTRIC POWER DISTRIBUTION SYSTEM AT PT PLN (Persero) UP3 SOUTH MAKASSAR ULP KALEBAJENG USING ETAP
View through CrossRef
Short circuit fault analysis is needed to determine the amount of short circuit current flowing in a system. This study discusses the single-phase short-circuit current to the ground at the point where the disturbance occurs from the base of the network to the end of the Malewang feeder network. The purpose of this study was to determine the amount of short circuit fault current in the Electric Power Distribution System at PT PLN (Persero) UP3 South Makassar ULP Kalebajeng. This study used the ETAP program and manual calculations. The results of the study found that the contribution of the largest single-phase short-circuit fault current to the ground in the Malewang feeder occurred on Buses located at the base of the network close to the Substation, namely Bus 1 (Exim-Rec Kalaserena) of 0.311 kA, while thesmallest Buscontribution occurred on Buses located at the end of the network far from the Substation, namely Buses 14 (Bilonga) of 0.292 kA. From the results of the study, it can be concluded that the farther the interference bus is from the Substation, the greater the channel impedance. The greater the impedance, the smaller the short-circuit current.
Fakultas Teknik, Universitas Negeri Makassar
Title: SHORT CIRCUIT FAULT ANALYSIS IN THE ELECTRIC POWER DISTRIBUTION SYSTEM AT PT PLN (Persero) UP3 SOUTH MAKASSAR ULP KALEBAJENG USING ETAP
Description:
Short circuit fault analysis is needed to determine the amount of short circuit current flowing in a system.
This study discusses the single-phase short-circuit current to the ground at the point where the disturbance occurs from the base of the network to the end of the Malewang feeder network.
The purpose of this study was to determine the amount of short circuit fault current in the Electric Power Distribution System at PT PLN (Persero) UP3 South Makassar ULP Kalebajeng.
This study used the ETAP program and manual calculations.
The results of the study found that the contribution of the largest single-phase short-circuit fault current to the ground in the Malewang feeder occurred on Buses located at the base of the network close to the Substation, namely Bus 1 (Exim-Rec Kalaserena) of 0.
311 kA, while thesmallest Buscontribution occurred on Buses located at the end of the network far from the Substation, namely Buses 14 (Bilonga) of 0.
292 kA.
From the results of the study, it can be concluded that the farther the interference bus is from the Substation, the greater the channel impedance.
The greater the impedance, the smaller the short-circuit current.
Related Results
Integration Techniques of Fault Detection and Isolation Using Interval Observers
Integration Techniques of Fault Detection and Isolation Using Interval Observers
An interval observer has been illustrated to be a suitable approach to detect and isolate faults affecting complex dynamical industrial systems.
Concerning fault detection, interv...
PENGARUH KUALITAS PELAYANAN TERHADAP KEPUASAN PELANGGAN PLN RAYON KEDIRI KOTA (STUDI KASUS PEMBAYARAN REKENING LISTRIK DI PLN RAYON KEDIRI KOTA)
PENGARUH KUALITAS PELAYANAN TERHADAP KEPUASAN PELANGGAN PLN RAYON KEDIRI KOTA (STUDI KASUS PEMBAYARAN REKENING LISTRIK DI PLN RAYON KEDIRI KOTA)
This study aims to determine how high the level of customer satisfaction with the service of PLN Rayon Kediri Kota, to determine the quality of service to customer satisfaction PLN...
Simulation modeling study on short circuit ability of distribution transformer
Simulation modeling study on short circuit ability of distribution transformer
Abstract
Under short circuit condition, the oil immersed distribution transformer will endure combined electro-thermal stress, eventually lead to the mechanical dama...
Decomposition and Evolution of Intracontinental Strike‐Slip Faults in Eastern Tibetan Plateau
Decomposition and Evolution of Intracontinental Strike‐Slip Faults in Eastern Tibetan Plateau
Abstract:Little attention had been paid to the intracontinental strike‐slip faults of the Tibetan Plateau. Since the discovery of the Longriba fault using re‐measured GPS data in 2...
Analisis Efektivitas Kerja Karyawan Divisi Yan HC PT. PLN (Persero)
Analisis Efektivitas Kerja Karyawan Divisi Yan HC PT. PLN (Persero)
Purpose – This study aims to determine whether the performance of Yan HC division employees at PT. PLN (Persero) has been effective. Methodology – The method used is observation, d...
PENGARUH PELATIHAN TERHADAP KINERJA KARYAWAN PT. DAHANA (PERSERO) SUBANG
PENGARUH PELATIHAN TERHADAP KINERJA KARYAWAN PT. DAHANA (PERSERO) SUBANG
Karyawan sebagai aset perusahaan dengan peranannya yang sangat menentukan berhasil tidaknya perusahaan dalam mencapai tujuannya. Dalam memperoleh karyawan yang berkinerja baik peru...
Evaluasi Ketidakseimbangan Beban Pada Penyulang Unicora
Evaluasi Ketidakseimbangan Beban Pada Penyulang Unicora
Load imbalance in electrical distribution transformers can lead to significant power losses and decreased efficiency in electrical distribution systems. This study focuses on the l...
Efektivitas Pelayanan Ketenagalistrikan melalui Aplikasi PLN Mobile dalam Menangani Keluhan
Efektivitas Pelayanan Ketenagalistrikan melalui Aplikasi PLN Mobile dalam Menangani Keluhan
Abstract. Service is an important thing in the implementation of public services. In this pandemic period, more services are provided through digital-based applications than conven...