Study on the optimum value of remanent magnetism for suppressing ferromagnetic resonance of voltage transformer in all-cable line
View through CrossRef
Introduction: Due to the need for safety and aesthetics, 10 kV urban power grids are gradually dominated by all-cable lines. However, this trend also brings new challenges. Cables, which are equivalent to capacitors at industrial frequency, are prone to resonate with the voltage transformers (PTs) in the system, causing drastic changes in current and voltage and posing a threat to the stable operation of the system. In addition, the intrusion of lightning waves into the substation will lead to different residual magnetization in the PT core, which further changes the core inductance value and affects the ferromagnetic resonance of the system to a certain extent.Methods: In order to deeply investigate the influence of remanent magnetism on the ferromagnetic resonance of the system, this paper establishes a simulation model of a 10 kV all-cable line based on the PSCAD software, and adopts a UMEC transformer capable of simulating the saturation characteristics to construct the PT, and simulates the intrusion currents by using a DC current source in order to generate remanent magnetism. By this method, the effect of remanent magnetization on the ferromagnetic resonance of the system is explored at different magnitudes and directions.Results: The results of the study show that the residual magnetization has a significant effect on the ferromagnetic resonant inrush current of the voltage transformer. When the remanent magnetization value is positive and less than 0.6 pu, the ferromagnetic resonance inrush current of PT can be effectively suppressed, and the smaller the remanent magnetization value is, the better the suppression effect is. However, negative remanent magnetization cannot suppress the ferromagnetic resonance of the PT, but may exacerbate the inrush current, leading to more serious consequences.Conclusion: This study helps to improve the stability of the power grid and also provides a valuable reference for future grid design and maintenance.
Title: Study on the optimum value of remanent magnetism for suppressing ferromagnetic resonance of voltage transformer in all-cable line
Description:
Introduction: Due to the need for safety and aesthetics, 10 kV urban power grids are gradually dominated by all-cable lines.
However, this trend also brings new challenges.
Cables, which are equivalent to capacitors at industrial frequency, are prone to resonate with the voltage transformers (PTs) in the system, causing drastic changes in current and voltage and posing a threat to the stable operation of the system.
In addition, the intrusion of lightning waves into the substation will lead to different residual magnetization in the PT core, which further changes the core inductance value and affects the ferromagnetic resonance of the system to a certain extent.
Methods: In order to deeply investigate the influence of remanent magnetism on the ferromagnetic resonance of the system, this paper establishes a simulation model of a 10 kV all-cable line based on the PSCAD software, and adopts a UMEC transformer capable of simulating the saturation characteristics to construct the PT, and simulates the intrusion currents by using a DC current source in order to generate remanent magnetism.
By this method, the effect of remanent magnetization on the ferromagnetic resonance of the system is explored at different magnitudes and directions.
Results: The results of the study show that the residual magnetization has a significant effect on the ferromagnetic resonant inrush current of the voltage transformer.
When the remanent magnetization value is positive and less than 0.
6 pu, the ferromagnetic resonance inrush current of PT can be effectively suppressed, and the smaller the remanent magnetization value is, the better the suppression effect is.
However, negative remanent magnetization cannot suppress the ferromagnetic resonance of the PT, but may exacerbate the inrush current, leading to more serious consequences.
Conclusion: This study helps to improve the stability of the power grid and also provides a valuable reference for future grid design and maintenance.
Related Results
Automatic Load Sharing of Transformer
Automatic Load Sharing of Transformer
Transformer plays a major role in the power system. It works 24 hours a day and provides power to the load. The transformer is excessive full, its windings are overheated which lea...
High frequency modeling of power transformers under transients
High frequency modeling of power transformers under transients
This thesis presents the results related to high frequency modeling of power transformers. First, a 25kVA distribution transformer under lightning surges is tested in the laborator...
Deep Learning Training Model Construction and Optimization of Cable Size Features in 3D Point Cloud Data
Deep Learning Training Model Construction and Optimization of Cable Size Features in 3D Point Cloud Data
Cables are widely used in power transmission, and the measurement of key dimensions of cables is an indispensable part of the cable preparation process to help ensure their quality...
Natural vibration and wind-induced response analysis of the non-fully symmetric Geiger cable dome
Natural vibration and wind-induced response analysis of the non-fully symmetric Geiger cable dome
Cable dome is a special flexible structure made of cable strut beam and membrane. Non-fully symmetric Geiger cable dome is a new Geiger cable dome with the characteristics of eight...
Wireline Cable Dynamics and Wellbore Diagnostics in the Deepwater Logging Environment
Wireline Cable Dynamics and Wellbore Diagnostics in the Deepwater Logging Environment
The evolving complexity of deepwater wellbores has created new challenges and risks for wireline evaluation. Geometries and depths challenge the foundational assumptions of traditi...
Modelado de un Recuperador Dinámico de Tensión para el Mejoramiento de la Calidad de la Onda de Tensión
Modelado de un Recuperador Dinámico de Tensión para el Mejoramiento de la Calidad de la Onda de Tensión
[1] R. C. Dugan, H. W. Beaty, y S. Santoso, Electrical Power Systems Quality, Third edition. Tata McGraw Hill Education, 2012.[2] J. Arrilaga y N. R. Watson, Powe...
Comparison of Local Volt/var Control Strategies for PV Hosting Capacity Enhancement of Low Voltage Feeders
Comparison of Local Volt/var Control Strategies for PV Hosting Capacity Enhancement of Low Voltage Feeders
The PV hosting capacity of low voltage feeders is restricted by voltage and current limits, and in many cases, voltage limit violations are the limiting factor for photovoltaic int...
Cable Steady-State Ampacity Correction Method based on Multi Physical Field Coupling Algorithm
Cable Steady-State Ampacity Correction Method based on Multi Physical Field Coupling Algorithm
The difference between the single air laying ampacity test value of medium voltage power cable and the system ampacity of three-phase laying and operation is a common problem in th...