Equipment Performance Due to Voltage Sags – Test Results for Contactor and Induction Motor

View through CrossRef
AbstractThis paper presents experimental test results of contactor and induction motor performances when they were supplied by voltage sags. A Programmable source is used to generate various voltage sag characteristics. A small of contactor and induction motor were used for this purpose. Test results show that magnitude and duration are very important aspects that determine performance of the equipments. Influence of other characteristics such as point on wave and repetitive of voltage sag are discussed. Difference of point on wave of sag initiation will cause contactor performance is different for tripping. The occurrence of the second sag after the first one may affect the contactor performance. The contactor performance becomes sensitive when it is supplied by repetitive voltage sags. Voltage sag cause transient current drawn by the motor is too high and it occurs at recovery voltage instant and the value depending on magnitude of the sags. The current peak is not significant influenced by sag duration. The current peak in the second sag is similar to first sag. Therefore presence repetitive of voltage sags on induction motor is not influence on the current peaks.
Title: Equipment Performance Due to Voltage Sags – Test Results for Contactor and Induction Motor
Description:
AbstractThis paper presents experimental test results of contactor and induction motor performances when they were supplied by voltage sags.
A Programmable source is used to generate various voltage sag characteristics.
A small of contactor and induction motor were used for this purpose.
Test results show that magnitude and duration are very important aspects that determine performance of the equipments.
Influence of other characteristics such as point on wave and repetitive of voltage sag are discussed.
Difference of point on wave of sag initiation will cause contactor performance is different for tripping.
The occurrence of the second sag after the first one may affect the contactor performance.
The contactor performance becomes sensitive when it is supplied by repetitive voltage sags.
Voltage sag cause transient current drawn by the motor is too high and it occurs at recovery voltage instant and the value depending on magnitude of the sags.
The current peak is not significant influenced by sag duration.
The current peak in the second sag is similar to first sag.
Therefore presence repetitive of voltage sags on induction motor is not influence on the current peaks.

Related Results

Assessment and Mitigation Studies of Voltage Sags during Sympathetic Inrush Current
Assessment and Mitigation Studies of Voltage Sags during Sympathetic Inrush Current
The system voltage may be negatively impacted by the transformer’s energisation which draws a large value of magnetising inrush current for a few seconds. During the transformer’s ...
Sliding Mode Controlled drives for wide speed operation of Threephase Induction Motor
Sliding Mode Controlled drives for wide speed operation of Threephase Induction Motor
Induction motor is widely used due to advantages in terms of performance, size, maintenance and efficiency compared to dc motor. Induction motor is either Scalar Controlled or Vect...
Methodology for Determination of the Number of Equipment Malfunctions Due to Voltage Sags
Methodology for Determination of the Number of Equipment Malfunctions Due to Voltage Sags
This article deals with the assessment of the reliability of sensitive equipment due to voltage sags. The most frequent problems of power quality are voltage sags. Equipment that c...
Assessing the Financial Impact and Mitigation Methods for Voltage Sag in Power Grid
Assessing the Financial Impact and Mitigation Methods for Voltage Sag in Power Grid
Voltage sags, as defined by the IEEE Standard, refer to sudden drops in voltage magnitude that last for a duration greater than 0.5 cycles of the power frequency but less than or e...
Evaluation of Different Methods for Voltage Sag Source Detection
Evaluation of Different Methods for Voltage Sag Source Detection
This paper compares and evaluates three different methods for voltage sag source detection. First method (method I) is based on the assumption, that the energy flow at the monitori...
Impacts of voltage sags and protection coordination on sensitive equipment in distribution systems
Impacts of voltage sags and protection coordination on sensitive equipment in distribution systems
Nowadays, a lot of sensitive electronic equipment is widely used in modern power systems such as power converters and adjustable speed drivers. Voltage sag has gained more interest...
Modelado de un Recuperador Dinámico de Tensión para el Mejoramiento de la Calidad de la Onda de Tensión
Modelado de un Recuperador Dinámico de Tensión para el Mejoramiento de la Calidad de la Onda de Tensión
[1]          R. C. Dugan, H. W. Beaty, y S. Santoso, Electrical Power Systems Quality, Third edition. Tata McGraw Hill Education, 2012.[2]          J. Arrilaga y N. R. Watson, Powe...