CALIBRATION OF EXPERIMENTAL INSTALLATION FOR MEASURING PARTIAL DISCHARGES IN LOW CAPACITANCE INSULATION SAMPLES
View through CrossRef
Purpose. The method for calibrating an experimental installation for studying the patterns of partial discharges aris-ing in samples of paper insulation having low capacitance was developed. Methodology. In order to verify the proposed method, a physical experiment was carried out in a high-voltage laboratory to measure partial discharge parameters using a digital oscilloscope. Free software for circuit simulation was used to create high-pass filter schematics. Results. The task of calibrating the systems for measuring partial discharges of low capacitance insulation samples (for example, ranging from 1 pF to 5 pF) is characterized by high complexity, because the calibration capacitor must have a capacitance an order of magnitude smaller than the capacitance of the test sample (from 0.1 pF to 0.5 pF, accordingly), which sometimes cannot be achieved practically. Moreover, in such case the stray capacitance will obviously be of the same order as the capacitance of calibration capacitor, or even greater. In such cases traditional calibration circuits where calibration generator is connected in parallel with the test object cannot be applied. Originality. Alternate calibration circuit was proposed, implemented and tested in the work, where the calibration generator is connected in series with test object. Practical value. Studies of the proposed calibration method have shown that it can be used quite effectively in cases when test object have low capacitance. The results of recording the calibration pulses showed that they can be reliably recorded and measured with a minimum error (oscilloscope error), and errors associated with parasitic parameters of the recording circuit are automatically taken into account when calibrating by this method and do not require additional adjustments. Conclusions. There is a possibility to increase the sensitivity of the measuring circuit to 0.05 pC/V, primarily by increasing the gain of the oscilloscope at least 100 times without repeating the calibration procedure. This will make it possible to study insulation samples of fairly high quality in which the level of partial discharges is much lower than in those samples used in this work. The experimental installation can be used to analyze different ways of modeling partial discharges on a personal computer and comparing their results with a real experiment. References 15, figures 12.
Publishing House Helvetica (Publications)
Title: CALIBRATION OF EXPERIMENTAL INSTALLATION FOR MEASURING PARTIAL DISCHARGES IN LOW CAPACITANCE INSULATION SAMPLES
Description:
Purpose.
The method for calibrating an experimental installation for studying the patterns of partial discharges aris-ing in samples of paper insulation having low capacitance was developed.
Methodology.
In order to verify the proposed method, a physical experiment was carried out in a high-voltage laboratory to measure partial discharge parameters using a digital oscilloscope.
Free software for circuit simulation was used to create high-pass filter schematics.
Results.
The task of calibrating the systems for measuring partial discharges of low capacitance insulation samples (for example, ranging from 1 pF to 5 pF) is characterized by high complexity, because the calibration capacitor must have a capacitance an order of magnitude smaller than the capacitance of the test sample (from 0.
1 pF to 0.
5 pF, accordingly), which sometimes cannot be achieved practically.
Moreover, in such case the stray capacitance will obviously be of the same order as the capacitance of calibration capacitor, or even greater.
In such cases traditional calibration circuits where calibration generator is connected in parallel with the test object cannot be applied.
Originality.
Alternate calibration circuit was proposed, implemented and tested in the work, where the calibration generator is connected in series with test object.
Practical value.
Studies of the proposed calibration method have shown that it can be used quite effectively in cases when test object have low capacitance.
The results of recording the calibration pulses showed that they can be reliably recorded and measured with a minimum error (oscilloscope error), and errors associated with parasitic parameters of the recording circuit are automatically taken into account when calibrating by this method and do not require additional adjustments.
Conclusions.
There is a possibility to increase the sensitivity of the measuring circuit to 0.
05 pC/V, primarily by increasing the gain of the oscilloscope at least 100 times without repeating the calibration procedure.
This will make it possible to study insulation samples of fairly high quality in which the level of partial discharges is much lower than in those samples used in this work.
The experimental installation can be used to analyze different ways of modeling partial discharges on a personal computer and comparing their results with a real experiment.
References 15, figures 12.
Related Results
(Invited) Strategies for Calibration Cost Reduction in Heterogeneous Chemical Sensor Arrays
(Invited) Strategies for Calibration Cost Reduction in Heterogeneous Chemical Sensor Arrays
Introduction
Heterogeneous gas sensor arrays coupled with machine learning algorithms have been proposed for a wide range of applications. However, i...
Thermal Performance and Building Energy Simulation of Precast Insulation Walls in Two Climate Zones
Thermal Performance and Building Energy Simulation of Precast Insulation Walls in Two Climate Zones
Traditional concrete buildings exhibit low energy consumption and high heat loss, which results in a larger environmental problem. Precast insulation walls are proposed for strengt...
The false alarms and ‘non-impacting’ discharges from event duration monitors (EDM) by a UK water company
The false alarms and ‘non-impacting’ discharges from event duration monitors (EDM) by a UK water company
Abstract
Sewage discharges to aquatic environments present a real danger to human and ecosystem health. Event duration monitors (EDMs) from combined stormwater overflows (C...
Characteristics of after‐discharges following compound muscle action potential or F‐wave in primary peripheral nerve hyperexcitability syndrome
Characteristics of after‐discharges following compound muscle action potential or F‐wave in primary peripheral nerve hyperexcitability syndrome
AbstractIntroduction/AimsF‐wave testing frequently reveals after‐discharges of varied morphologies in patients with primary peripheral nerve hyperexcitability syndrome (PNHS), alth...
SS: Spar Technology- Developments in Deepwater spar installation
SS: Spar Technology- Developments in Deepwater spar installation
Abstract
During the last seven years Heerema Marine Contractors (HMC) has installed more than half of all Spars in the deep waters of the Gulf of Mexico. The dual...
Radiometric cross-calibration of Sentinel-2B MSI with HY-1C SCS based on the near simultaneous imaging of common ground targets
Radiometric cross-calibration of Sentinel-2B MSI with HY-1C SCS based on the near simultaneous imaging of common ground targets
To simplify the cross-calibration process and improve calibration frequency and accuracy, this paper proposes a cross-calibration method for the multispectral remote sensor Multi-S...
ČVRSTA IZOLACIJA ENERGETSKIH TRANSFOMATORA – STRUKTURA, PRIMENSKE OSOBINE I METODE ISPITIVANjA NAKON FABRIČKOG SUŠENjA I TOKOM EKSPLOATACIJE
ČVRSTA IZOLACIJA ENERGETSKIH TRANSFOMATORA – STRUKTURA, PRIMENSKE OSOBINE I METODE ISPITIVANjA NAKON FABRIČKOG SUŠENjA I TOKOM EKSPLOATACIJE
Transformers are vital components in electricity transmission and distribution systems. The lifetime of transformers is limited by the lifetime of solid insulation, which is mostly...
Automatic Hand-Eye Calibration Method of Welding Robot Based on Linear Structured Light
Automatic Hand-Eye Calibration Method of Welding Robot Based on Linear Structured Light
Aiming at solving the problems such as long calibration time, low precision, and complex operation in hand-eye calibration of welding robot, an automatic hand-eye calibration algor...