Analisis Penggunaan Transformator Sisipan Untuk Mengatasi Rugi Tegangan dan Pembebanan Lebih
View through CrossRef
On the JD267 distribution transformer with a capacity of 100 kVA at the Kalibaru feeder on the PT PLN (Persero) ULP Genteng experienced overloading at WBP (88.03%) and high voltage losses. The magnitude of the load exceeds 80% of the standard transformer capacity and is in the bad category (load >= 80%) according to Table I. SE No. 0017.E/DIR/2014, related to transformer loading percentage. Meanwhile, the voltage loss of the JD267 transformer when the WBP is in Phase R is 19.05%, Phase S is 17.08%, and Phase T is 18.33%. This exceeds the voltage tolerance limit in SPLN 1:1995 that the voltage is not allowed to exceed +5% and -10% of the PLN standard voltage, namely 220 V. To handle this problem, PT. PLN (Persero) ULP Genteng carried out the installation of insert transformers by estimating load growth in the next 5 years using the Least Square method. After the addition of the insert transformer, the loading on the JD267 distribution transformer fell to 58.93% on WBP. Meanwhile, the magnitude of the JD267 transformer voltage loss when the WBP after insertion in the R Phase decreases to 0.84%, the S Phase is 1.04%, and the T Phase is 1.63%, and when the LWBP after insertion in the R Phase decreases to 0 .76%, S Phase 0.30%, and T Phase 0.6%. Based on the data above, adding an insert transformer can improve the loading percentage on the transformer and reduce voltage losses that occur at the end voltage of the transformer.
Politeknik Negeri Malang
Title: Analisis Penggunaan Transformator Sisipan Untuk Mengatasi Rugi Tegangan dan Pembebanan Lebih
Description:
On the JD267 distribution transformer with a capacity of 100 kVA at the Kalibaru feeder on the PT PLN (Persero) ULP Genteng experienced overloading at WBP (88.
03%) and high voltage losses.
The magnitude of the load exceeds 80% of the standard transformer capacity and is in the bad category (load >= 80%) according to Table I.
SE No.
0017.
E/DIR/2014, related to transformer loading percentage.
Meanwhile, the voltage loss of the JD267 transformer when the WBP is in Phase R is 19.
05%, Phase S is 17.
08%, and Phase T is 18.
33%.
This exceeds the voltage tolerance limit in SPLN 1:1995 that the voltage is not allowed to exceed +5% and -10% of the PLN standard voltage, namely 220 V.
To handle this problem, PT.
PLN (Persero) ULP Genteng carried out the installation of insert transformers by estimating load growth in the next 5 years using the Least Square method.
After the addition of the insert transformer, the loading on the JD267 distribution transformer fell to 58.
93% on WBP.
Meanwhile, the magnitude of the JD267 transformer voltage loss when the WBP after insertion in the R Phase decreases to 0.
84%, the S Phase is 1.
04%, and the T Phase is 1.
63%, and when the LWBP after insertion in the R Phase decreases to 0 .
76%, S Phase 0.
30%, and T Phase 0.
6%.
Based on the data above, adding an insert transformer can improve the loading percentage on the transformer and reduce voltage losses that occur at the end voltage of the transformer.
Related Results
ANALISA PENGARUH PEMBEBANAN TERHADAP EFISIENSI DAN USIA PAKAI TRANSFORMATOR PADA PENYULANG BANDARA 2
ANALISA PENGARUH PEMBEBANAN TERHADAP EFISIENSI DAN USIA PAKAI TRANSFORMATOR PADA PENYULANG BANDARA 2
Beban yang bersifat fluktuatif dapat menimbulkan rugi-rugi pada transformator. Ketika suatu transformator diberi energi akan timbul rugi-rugi inti, rugi-rugi kumparan dan rugi-rugi...
Analisa Pengaruh Tegangan Harmonik Terhadap Regulasi Tegangan Eksitasi Generator Satu Fasa
Analisa Pengaruh Tegangan Harmonik Terhadap Regulasi Tegangan Eksitasi Generator Satu Fasa
Esensinya setiap generator listrik satu fasa maupun tiga fasa telah dilengkapi dengan sistem eksitasi. Sistem eksitasi generator ada tiga, yaitu sistem eksitasi statis, dinamis, da...
Analisis Rugi Tegangan Jaringan Distribusi 20 KV Pada PT. PLN (Persero) Cabang Merauke
Analisis Rugi Tegangan Jaringan Distribusi 20 KV Pada PT. PLN (Persero) Cabang Merauke
Sistem Distribusi merupakan salah satu bagian penting dalam penyaluran energi listrik. Dalam penyalurannya, energi listrik yang disalurkan tidak seluruhnya diterima oleh konsumen. ...
ANALISIS PENGARUH PURIFIKASI OLI TRANSFORMATOR TERHADAP TEGANGAN TEMBUS TRANSFORMATOR DISTRIBUSI
ANALISIS PENGARUH PURIFIKASI OLI TRANSFORMATOR TERHADAP TEGANGAN TEMBUS TRANSFORMATOR DISTRIBUSI
Penelitian ini adalah penelitian deskriptif kuantitatif yang bertujuan mengetahui pengaruh purifikasi terhadap peningkatan tegangan tembus oli transformator di PT Darma Karya Elekt...
Pengaruh Variasi Pembebanan Pada Kinerja Transformator 60 MVA di PT. PLN Gardu Induk Keramasan
Pengaruh Variasi Pembebanan Pada Kinerja Transformator 60 MVA di PT. PLN Gardu Induk Keramasan
Gardu Induk Keramasan melayani sistem distribusi tenaga listrik dengan pola pembebanan yang bersifat fluktuatif setiap harinya. Fluktuasi beban tersebut berpotensi menimbulkan rugi...
FAKTOR-FAKTOR YANG MEMPENGARUHI MORTALITAS PADA PASIEN DENGAN FRAKTUR COSTA: Literature Review
FAKTOR-FAKTOR YANG MEMPENGARUHI MORTALITAS PADA PASIEN DENGAN FRAKTUR COSTA: Literature Review
FAKTOR-FAKTOR YANG MEMPENGARUHI MORTALITAS PADA PASIEN DENGAN FRAKTUR COSTA: Literature Review Anna Tri Wahyuni1), Masfuri2), Liya Arista3)1,2,3 Fakultas Ilmu Keperawatan Univers...
supriyatna ANALISIS KOORDINASI ISOLASI DI GARDU INDUK KUTA TERHADAP TEGANGAN LEBIH AKIBAT SAMBARAN PETIR PADA SALURAN TRANSMISI 150 KV (Pak Supriyatna)
supriyatna ANALISIS KOORDINASI ISOLASI DI GARDU INDUK KUTA TERHADAP TEGANGAN LEBIH AKIBAT SAMBARAN PETIR PADA SALURAN TRANSMISI 150 KV (Pak Supriyatna)
Sambaran petir pada saluran transmisi 150 kV dapat menimbulkan tegangan lebih yang akan membahayakan peralatan jika tegangan tersebut melampaui tingkat isolasi dasar peralatan (TID...