Environmental sampling for legionella proliferation risk in three long-term care facilities in Vancouver, British Columbia
View through CrossRef
Background: Legionella is a pathogen that causes Legionnaires’ disease in high risk populations. The pathogen is known to exist in plumbing systems that do not have preventative factors in place to prevent its growth and proliferation. Legionella grows between 25˚C and 42˚C and is killed at 60˚C, yet long-term care facilities (LTCFs) reduce accessible hot water temperatures from 60˚C at the hot water tank to less than 49˚C at the taps in order to prevent scalding of their residents. Currently, prevention against scalding takes precedence as temperature at accessible taps is regulated within the Residential Care Regulation (RCR) of the Community Care and Assisted Living Act. It is thought that Legionella proliferation risk can be balanced with scalding in-part through the appropriate installation location of thermostatic mixing valves (TMVs). Methods: Three LTCFs in Vancouver, British Columbia were selected for environmental sampling for Legionella proliferation risk. At each LTCF the author recorded the type of hot water tank, temperature of water within the hot water tank, the presence of a TMV and temperature of pipes before and after the TMV. As well, the author recorded hot water temperatures after one minute and free available chlorine concentration ([FAC]) at numerous resident-accessible taps throughout each LTCF. Results: The hot water tank temperatures were set at 60.6˚C, 73.0˚C and 62.0˚C for LTCF #1, LTCF #2 and LTCF #3, respectively. All three LTCFs had installed a TMV within the boiler room immediately after the hot water tank. It was found that LTCF #1’s plumbing system water temperature was reduced from 60.6˚C (at the tank) to 48.9˚C after the TMV. LTCF #2’s plumbing system water temperature was reduced from 73.0˚C (at the tank) to 43.3˚C after the TMV. LTCF #3 was an older plumbing system that did not have thermometers within the boiler room to check the drop in temperature after the TMV. Water temperatures at taps were compared to a standard of 49°C and [FAC] levels at taps to a standard of 0.2 mg/L. The mean hot water temperature and mean [FAC] residual for all three LTCFs were 40.2˚C and 0.27 mg/L, respectively. For all three LTCFs, it was statistically significant that mean water temperatures were less than the comparison value of 49˚C (LTCF #1 p = 0.00000, LTCF #2 p = 0.00022, LTCF #3 p = 0.00110). It was also statistically significant that the mean [FAC] of all three LTCFs were greater than the comparison vale of 0.20 mg/L (LTCF #1 p = 0.00042, LTCF #2 p = 0.00000, LTCF #3 p = 0.00107). Conclusion: It was found that all three LTCFs had set preventive measures in place to protect their residents. Water was heated to at least 60˚C to prevent Legionella and lowered to less than 49˚C to prevent scalding. [FAC] residual was also adequate to prevent growth of Legionella. However, the location of the TMV in the boiler room was suspected to be a possible contributing factor to Legionella growth, especially if cold water temperatures were to reach 20˚C or above, as they could in warm summer months. Further research is needed to determine the significance of the TMV location and the presence of Legionella.
British Columbia Institute of Technology (BCIT)
Title: Environmental sampling for legionella proliferation risk in three long-term care facilities in Vancouver, British Columbia
Description:
Background: Legionella is a pathogen that causes Legionnaires’ disease in high risk populations.
The pathogen is known to exist in plumbing systems that do not have preventative factors in place to prevent its growth and proliferation.
Legionella grows between 25˚C and 42˚C and is killed at 60˚C, yet long-term care facilities (LTCFs) reduce accessible hot water temperatures from 60˚C at the hot water tank to less than 49˚C at the taps in order to prevent scalding of their residents.
Currently, prevention against scalding takes precedence as temperature at accessible taps is regulated within the Residential Care Regulation (RCR) of the Community Care and Assisted Living Act.
It is thought that Legionella proliferation risk can be balanced with scalding in-part through the appropriate installation location of thermostatic mixing valves (TMVs).
Methods: Three LTCFs in Vancouver, British Columbia were selected for environmental sampling for Legionella proliferation risk.
At each LTCF the author recorded the type of hot water tank, temperature of water within the hot water tank, the presence of a TMV and temperature of pipes before and after the TMV.
As well, the author recorded hot water temperatures after one minute and free available chlorine concentration ([FAC]) at numerous resident-accessible taps throughout each LTCF.
Results: The hot water tank temperatures were set at 60.
6˚C, 73.
0˚C and 62.
0˚C for LTCF #1, LTCF #2 and LTCF #3, respectively.
All three LTCFs had installed a TMV within the boiler room immediately after the hot water tank.
It was found that LTCF #1’s plumbing system water temperature was reduced from 60.
6˚C (at the tank) to 48.
9˚C after the TMV.
LTCF #2’s plumbing system water temperature was reduced from 73.
0˚C (at the tank) to 43.
3˚C after the TMV.
LTCF #3 was an older plumbing system that did not have thermometers within the boiler room to check the drop in temperature after the TMV.
Water temperatures at taps were compared to a standard of 49°C and [FAC] levels at taps to a standard of 0.
2 mg/L.
The mean hot water temperature and mean [FAC] residual for all three LTCFs were 40.
2˚C and 0.
27 mg/L, respectively.
For all three LTCFs, it was statistically significant that mean water temperatures were less than the comparison value of 49˚C (LTCF #1 p = 0.
00000, LTCF #2 p = 0.
00022, LTCF #3 p = 0.
00110).
It was also statistically significant that the mean [FAC] of all three LTCFs were greater than the comparison vale of 0.
20 mg/L (LTCF #1 p = 0.
00042, LTCF #2 p = 0.
00000, LTCF #3 p = 0.
00107).
Conclusion: It was found that all three LTCFs had set preventive measures in place to protect their residents.
Water was heated to at least 60˚C to prevent Legionella and lowered to less than 49˚C to prevent scalding.
[FAC] residual was also adequate to prevent growth of Legionella.
However, the location of the TMV in the boiler room was suspected to be a possible contributing factor to Legionella growth, especially if cold water temperatures were to reach 20˚C or above, as they could in warm summer months.
Further research is needed to determine the significance of the TMV location and the presence of Legionella.
.
Related Results
Kinetic analysis of viable but nonculturable Legionella inactivation using ozone
Kinetic analysis of viable but nonculturable Legionella inactivation using ozone
Legionnaires’ disease remains a serious health problem globally, caused
by the Gram-negative bacteria Legionella. The study objective was to
characterize the ability of ozone to ki...
The transmission mode of Legionella from its source
The transmission mode of Legionella from its source
Abstract
BackgroundLegionella pneumonia has a fatality rate of 28%.Methodsmicroscope, fluorescence Quantitative Polymerase Chain Reaction (qPCR), force mathematical analysi...
The effect of temperature and chlorine residual on the presence of Legionella spp. in water systems of public and tourist facilities
The effect of temperature and chlorine residual on the presence of Legionella spp. in water systems of public and tourist facilities
Introduction: Legionella bacteria are ubiquitous microorganisms mostly found in artificial water environments, especially those which produce aerosol, such as swimming pools, sauna...
Differentiation of Legionella pneumophila and Non-Legionella pneumophila Species by a Multiplex PCR Method
Differentiation of Legionella pneumophila and Non-Legionella pneumophila Species by a Multiplex PCR Method
Molecular techniques can be utilized as a rapid method to detect Legionella species in water samples with high accuracy. This study aimed to investigate the presence of Legionella ...
Environmental monitoring of Legionella in constructed water systems
Environmental monitoring of Legionella in constructed water systems
Abstract
Legionella is an opportunistic pathogen found in aquatic environments having profound health significance. Policy regulation mandates en...
Roads less travelled by—Pleistocene piracy in Washington’s northwestern Channeled Scabland
Roads less travelled by—Pleistocene piracy in Washington’s northwestern Channeled Scabland
ABSTRACT
The Pleistocene Okanogan lobe of Cordilleran ice in north-central Washington State dammed Columbia River to pond glacial Lake Columbia and divert the river ...
Legionellen in der Trinkwasser-Installation – Die Methode macht den Unterschied
Legionellen in der Trinkwasser-Installation – Die Methode macht den Unterschied
Legionella in drinking water installations – the method makes the difference Introduction: Legionella infections can cause Legionnaires’ disease, a severe form of pneumonia, as wel...
Expanding the Legionella pan-kinome
Expanding the Legionella pan-kinome
Abstract
The pathogenic Legionella bacteria are notorious for delivering numerous effector proteins into the host cell with the aim of disturbing and hijacking cellular pro...