Studi Kasus Integrasi Current Transformer (CT) dan EOCR untuk Pengamanan Arus pada Panel Cooling Tower Pump di PT DongJin Indonesia
View through CrossRef
Three-phase induction motors are essential components in industrial cooling systems that require reliable overcurrent protection to maintain operational continuity and prevent equipment damage. In the Cooling Tower Pump panel at PT DongJin Indonesia, a limitation was identified where the terminal of the Electronic Overcurrent Relay (EOCR) could not accommodate the 50 mm² power cable, preventing direct current measurement. This study aims to analyze the effectiveness of integrating a 200:5 A Current Transformer (CT) with the EOCR as an adaptive protection solution that is both safe and efficient. The research employs a case study approach through field observation, motor current measurement using a Fluke 303 Clamp Meter, and descriptive analysis of the recorded data. The results indicate that the three motors operate under stable load conditions, with current values ranging from 236.7 A to 275.7 A, while the secondary current detected by the EOCR ranges from 3.7 A to 3.9 A, consistent with the CT transformation ratio. During the starting phase, the current surged to 600.4 A without causing false tripping, demonstrating that the EOCR effectively distinguishes temporary inrush current from actual fault conditions. Therefore, the integration of CT–EOCR is proven to enhance measurement safety, maintain motor operational stability, and support efficient system maintenance in industrial environments.
Fakultas Hukum, Universitas Katolik Widya Karya Malang
Title: Studi Kasus Integrasi Current Transformer (CT) dan EOCR untuk Pengamanan Arus pada Panel Cooling Tower Pump di PT DongJin Indonesia
Description:
Three-phase induction motors are essential components in industrial cooling systems that require reliable overcurrent protection to maintain operational continuity and prevent equipment damage.
In the Cooling Tower Pump panel at PT DongJin Indonesia, a limitation was identified where the terminal of the Electronic Overcurrent Relay (EOCR) could not accommodate the 50 mm² power cable, preventing direct current measurement.
This study aims to analyze the effectiveness of integrating a 200:5 A Current Transformer (CT) with the EOCR as an adaptive protection solution that is both safe and efficient.
The research employs a case study approach through field observation, motor current measurement using a Fluke 303 Clamp Meter, and descriptive analysis of the recorded data.
The results indicate that the three motors operate under stable load conditions, with current values ranging from 236.
7 A to 275.
7 A, while the secondary current detected by the EOCR ranges from 3.
7 A to 3.
9 A, consistent with the CT transformation ratio.
During the starting phase, the current surged to 600.
4 A without causing false tripping, demonstrating that the EOCR effectively distinguishes temporary inrush current from actual fault conditions.
Therefore, the integration of CT–EOCR is proven to enhance measurement safety, maintain motor operational stability, and support efficient system maintenance in industrial environments.
Related Results
FAKTOR-FAKTOR YANG MEMPENGARUHI MORTALITAS PADA PASIEN DENGAN FRAKTUR COSTA: Literature Review
FAKTOR-FAKTOR YANG MEMPENGARUHI MORTALITAS PADA PASIEN DENGAN FRAKTUR COSTA: Literature Review
FAKTOR-FAKTOR YANG MEMPENGARUHI MORTALITAS PADA PASIEN DENGAN FRAKTUR COSTA: Literature Review Anna Tri Wahyuni1), Masfuri2), Liya Arista3)1,2,3 Fakultas Ilmu Keperawatan Univers...
ANALISIS SISTEM PROTEKSI MOTOR POMPA AIR UMPAN BOILER MP 1101 MENGGUNAKAN EOCR-I3BZ
ANALISIS SISTEM PROTEKSI MOTOR POMPA AIR UMPAN BOILER MP 1101 MENGGUNAKAN EOCR-I3BZ
Motor pompa MP 1101 ini sebagai motor air umpan boiler yang mengalirkan air yang telah selesai melalui proses demineralisasi menuju ke boiler di bagian pemeliharaan III PT. Petroki...
PENGARUH PEMBEBANAN TERHADAP ARUS EKSITASI GENERATOR UNIT 2 PLTMH CURUG
PENGARUH PEMBEBANAN TERHADAP ARUS EKSITASI GENERATOR UNIT 2 PLTMH CURUG
Generator salah satu bagian dari sistem tenaga listrik yang digunakan untuk mengkon-versi energi mekanik yang berasal dari putaran turbin menjadi energi listrik dengan memanfaatkan...
POLA ARUS LAUT PERMUKAAN DI PERAIRAN TANJUNG TIRAM KONAWE SELATAN
POLA ARUS LAUT PERMUKAAN DI PERAIRAN TANJUNG TIRAM KONAWE SELATAN
Arus laut permukaan merupakan arus laut yang bergerak pada lapisan massa air permukaan. Beberapa faktor yang membangkitkan arus permukaan pada perairan sekitar pantai umumnya bersu...
THEORETICAL ANALYSIS OF A WET COOLING TOWER FOR FRESH WATER FROM PLUME AND ANALYZING AN INDUSTRIAL COOLING TOWER BASED ON RESULTS
THEORETICAL ANALYSIS OF A WET COOLING TOWER FOR FRESH WATER FROM PLUME AND ANALYZING AN INDUSTRIAL COOLING TOWER BASED ON RESULTS
A cooling tower is a heat rejection device which rejects waste heat to the atmosphere through the cooling of a water stream to a lower temperature. The stream of saturated exhaust ...
DAMPAK TEKNOLOGI TERHADAP PROSES BELAJAR MENGAJAR
DAMPAK TEKNOLOGI TERHADAP PROSES BELAJAR MENGAJAR
DAFTAR PUSTAKAAditama, M. H. R., & Selfiardy, S. (2022). Kehidupan Mahasiswa Kuliah Sambil Bekerja di Masa Pandemi Covid-19. Kidspedia: Jurnal Pendidikan Anak Usia Dini, 3(...
Automatic Load Sharing of Transformer
Automatic Load Sharing of Transformer
Transformer plays a major role in the power system. It works 24 hours a day and provides power to the load. The transformer is excessive full, its windings are overheated which lea...