Cooling Tower Resonance Mitigation Through Vibration Analysis.
View through CrossRef
Condition monitoring, or CM is the process of monitoring machinery parameters such as vibration and temperature trends at routine intervals, in order to identify any significant change which may indicate developing faults. Vibration Analysis may be considered as one of the most predominant CM techniques used industry wide to carry out predictive maintenance and analysis on rotating equipment. Fault conditions such as unbalance, misalignment, resonance, hydraulic and aerodynamic forces can be detected using a variety of vibration tests and analysis methods.
Saudi Aramco Shaybah NGL Recovery Plant Department experienced a failure on a cooling tower right angled gearbox during commissioning. The root cause identified was insufficient lubrication. Although this gearbox was fitted with online fixed instrumentation, set points were too lenient. However, offline vibration troubleshooting techniques highlighted a resonance issue and provided the necessary data to rectify and resolve the high vibration on the fan.
Mitigation steps taken included a thorough evaluation of the existing gearbox protection design and Velometer selection. Further vibration data was collected with a portable device for two main reasons: firstly for comparison with the fixed Velometer readings and secondly to measure in the horizontal axis, which is perpendicular to the fixed position. Higher amplitudes were recorded in the horizontal axis as the vertical position where the Velometer is fixed, due to the orientation of the gearbox supporting beam. Resonance or bump tests were conducted on the gearbox to investigate the elevated amplitudes recorded in the horizontal plane. Bump tests proved that the natural frequency of the gearbox coincided with the cooling fans blade pass frequency (BPF). Resonance was proven, therefore had to be addressed in order to avoid component deterioration and imminent failure. Cost and repair or down time was paramount in finding the solution and implementation on all four cooling fans. Fundamentally, the most effective solution was to separate the fan blade pass and the natural frequencies of the right angled gearbox. Removing a resonance condition would reduce the overall vibration amplitude and extend the component life span of the cooling tower rotating parts.
This paper will detail the steps taken to investigate and rectify the mechanical failure. In addition it will discuss the relevance of an effective predictive maintenance strategy and the importance of verifying the design of fixed or permanent instrumentation.
Title: Cooling Tower Resonance Mitigation Through Vibration Analysis.
Description:
Condition monitoring, or CM is the process of monitoring machinery parameters such as vibration and temperature trends at routine intervals, in order to identify any significant change which may indicate developing faults.
Vibration Analysis may be considered as one of the most predominant CM techniques used industry wide to carry out predictive maintenance and analysis on rotating equipment.
Fault conditions such as unbalance, misalignment, resonance, hydraulic and aerodynamic forces can be detected using a variety of vibration tests and analysis methods.
Saudi Aramco Shaybah NGL Recovery Plant Department experienced a failure on a cooling tower right angled gearbox during commissioning.
The root cause identified was insufficient lubrication.
Although this gearbox was fitted with online fixed instrumentation, set points were too lenient.
However, offline vibration troubleshooting techniques highlighted a resonance issue and provided the necessary data to rectify and resolve the high vibration on the fan.
Mitigation steps taken included a thorough evaluation of the existing gearbox protection design and Velometer selection.
Further vibration data was collected with a portable device for two main reasons: firstly for comparison with the fixed Velometer readings and secondly to measure in the horizontal axis, which is perpendicular to the fixed position.
Higher amplitudes were recorded in the horizontal axis as the vertical position where the Velometer is fixed, due to the orientation of the gearbox supporting beam.
Resonance or bump tests were conducted on the gearbox to investigate the elevated amplitudes recorded in the horizontal plane.
Bump tests proved that the natural frequency of the gearbox coincided with the cooling fans blade pass frequency (BPF).
Resonance was proven, therefore had to be addressed in order to avoid component deterioration and imminent failure.
Cost and repair or down time was paramount in finding the solution and implementation on all four cooling fans.
Fundamentally, the most effective solution was to separate the fan blade pass and the natural frequencies of the right angled gearbox.
Removing a resonance condition would reduce the overall vibration amplitude and extend the component life span of the cooling tower rotating parts.
This paper will detail the steps taken to investigate and rectify the mechanical failure.
In addition it will discuss the relevance of an effective predictive maintenance strategy and the importance of verifying the design of fixed or permanent instrumentation.
Related Results
Blades condition monitoring using shaft torsional vibration signals
Blades condition monitoring using shaft torsional vibration signals
PurposeThe purpose of this paper is to validate mathematically the feasibility of extracting the rotating blades vibration condition from the shaft torsional vibration measurement....
The Delta Tower: A Light, Compliant Tower for the Gulf of Mexico
The Delta Tower: A Light, Compliant Tower for the Gulf of Mexico
ABSTRACT
The concept which is described in the paper is applicable to fields located in the Gulf of Mexico in water depths ranging from 1 000 to 1 750 feet. The c...
Application of Machine Learning Based Meta Models for Predicting Film Cooling Effectiveness in Gas Turbine Blades
Application of Machine Learning Based Meta Models for Predicting Film Cooling Effectiveness in Gas Turbine Blades
Abstract
In Large Gas Turbines, turbine components in particular blades and vanes operate at significantly high temperatures. As a result, cooling of these component...
Numerical Simulation of Influence of Cross Wind on Performance of Different Sections of Indirect Air Cooling Tower
Numerical Simulation of Influence of Cross Wind on Performance of Different Sections of Indirect Air Cooling Tower
The cooling performances of the indirect dry air cooling tower depend on the performance of each section. In accordance with relevant design criteria and standards, the influence o...
Lena Guyed Tower Project Overview
Lena Guyed Tower Project Overview
ABSTRACT
The installation of the Lena guyed tower was one of the industry's most significant accomplishments of 1983. This paper serves as an introduction to a se...
Features of vibration mixers design
Features of vibration mixers design
The article presents the results of the analysis of vibration mixers designs, presents their classification. The classification is based on the principle of action and the method o...
Influence of the Flexible Tower on Aeroelastic Loads of the Wind Turbine
Influence of the Flexible Tower on Aeroelastic Loads of the Wind Turbine
Based on the two-node Euler-Bernoulli beam, the tower system is discretized by finite element method, and the cubic Hermite polynomial is taken as the shape function of the beam el...
Benguela-Belize Compliant Piled Tower: Tower Design
Benguela-Belize Compliant Piled Tower: Tower Design
Abstract
The compliant tower is a proven bottom-founded platform which has been used successfully for three developments in the Gulf of Mexico. The compliant towe...