The optimization of water distribution systems in high-rise buildings is essential for enhancing energy efficiency and reducing operational costs. This study examines the effects of implementing a Variable Frequency Drive (VFD) on a centrifugal pump system within a four-storey high-rise building at PT SBA. A case study approach was employed to measure key operational parameters—namely, electrical power consumption, water flow rate, and pressure distribution—both before and after VFD installation. The experimental results demonstrate that the VFD application resulted in a 20% reduction in power consumption, decreasing from 3.5 kW to 2.8 kW, while the water flow rate improved by 12.5%, rising from 80 LPM to 90 LPM. In addition, the pressure range was significantly stabilized, narrowing from 1.2–2.5 bar to 1.0–2.0 bar across the building’s floors. An economic analysis based on the observed energy savings indicates an annual cost reduction of approximately Rp7,665,000, with a corresponding return on investment achieved in less than one year. The findings suggest that integrating VFD technology into centrifugal pump systems not only enhances operational efficiency and extends equipment lifespan by mitigating load fluctuations but also offers substantial economic benefits. This study provides a robust framework for the broader application of VFD-based optimization strategies in high-rise and industrial water distribution systems.
Title: Power Optimisation of Centrifugal Pumps in a 4-Storey Building
Description:
The optimization of water distribution systems in high-rise buildings is essential for enhancing energy efficiency and reducing operational costs.
This study examines the effects of implementing a Variable Frequency Drive (VFD) on a centrifugal pump system within a four-storey high-rise building at PT SBA.
A case study approach was employed to measure key operational parameters—namely, electrical power consumption, water flow rate, and pressure distribution—both before and after VFD installation.
The experimental results demonstrate that the VFD application resulted in a 20% reduction in power consumption, decreasing from 3.
5 kW to 2.
8 kW, while the water flow rate improved by 12.
5%, rising from 80 LPM to 90 LPM.
In addition, the pressure range was significantly stabilized, narrowing from 1.
2–2.
5 bar to 1.
0–2.
0 bar across the building’s floors.
An economic analysis based on the observed energy savings indicates an annual cost reduction of approximately Rp7,665,000, with a corresponding return on investment achieved in less than one year.
The findings suggest that integrating VFD technology into centrifugal pump systems not only enhances operational efficiency and extends equipment lifespan by mitigating load fluctuations but also offers substantial economic benefits.
This study provides a robust framework for the broader application of VFD-based optimization strategies in high-rise and industrial water distribution systems.

Related Results

Effect of Aspect Ratio on High Rise Structures with Diagrid
Effect of Aspect Ratio on High Rise Structures with Diagrid
Urbanization and population explosion in the present times has led to increase in demand for land and residencies but the availability of land is scare i.e reason a trend has evolv...
De gevel – een intermediair element tussen buiten en binnen
De gevel – een intermediair element tussen buiten en binnen
This study is based on the fact that all people have a basic need for protection from other people (and animals) as well as from the elements (the exterior climate). People need a ...
Effect of Infill Wall on Plan Irregular Tall Structure
Effect of Infill Wall on Plan Irregular Tall Structure
In the present study, the behavior of plan irregular (C, T, I shaped irregular building and regular building) tall building subjected to the seismic load alongwith the importance o...
Der skal ikke lades sten på sten tilbage
Der skal ikke lades sten på sten tilbage
The Building by the Barbar TempleClose by the large temple at Barbar 1) lies a little tell, which was investigated in the spring of 1956. The tell was shown to cover a building of ...
Review of the Hydraulic and Structural Design of High-Speed Centrifugal Pumps
Review of the Hydraulic and Structural Design of High-Speed Centrifugal Pumps
In recent years, much attention has been paid to the application of high-speed centrifugal pumps; still, the development of this pump faces several challenges. In order to obtain a...
Design of mutli-storied building with and without soft stories using STAAD Pro
Design of mutli-storied building with and without soft stories using STAAD Pro
Soft stories are one of those structures containing structural irregularities, especially vertical irregularities. Soft stories case is generally related to sudden and abrupt chang...
Optimisation of power electronics for regulated transformer rectifier units
Optimisation of power electronics for regulated transformer rectifier units
This study presents a comprehensive approach for the design optimisation of passive components and heatsinks in power electronic converters. The design and selection of passive com...
Emerging Issues due to Adoption of Submersible Pump Technology in Marginal Quality Areas of Haryana
Emerging Issues due to Adoption of Submersible Pump Technology in Marginal Quality Areas of Haryana
Declining water table, indicative of overall negative ground water balance, has emerged as the most serious challenge to sustainability of irrigated agriculture in many states of I...

Back to Top