Microbial Assessment of Indoor Air Quality of Laboratory Sections in Obong University, Obong Ntak, Nigeria
View through CrossRef
Background: Poor indoor air quality constitutes a significant health problem in schools, mostly in the laboratory sections due to a high number of students per laboratory vis-a-vis space confinement, insufficient outside air supply, poor construction and maintenance of laboratory buildings. Aim: This study was carried out to assess the air quality and identify airborne bacteria and fungi in selected sections of Obong University Laboratory.
Materials and Methods: Institutional based study employing passive air sampling, settle plate or gravitational sampling method to collect airborne bacteria and fungi was conducted in 3 selected laboratory sections of the University. Culture, isolation, colony count/air quality assessment and identification of airborne bacteria and fungi were done using standard methods.
Results: The mean bacterial load was 111.75 CFU/m3 in the morning and 125.25 CFU/m3 in the afternoon. The highest and lowest bacterial loads were recorded at the Laboratory Animal Room (LAR) to be 165 CFU/m3 and 201 CFU/m3 in the morning and afternoon, respectively. The total fungal load was 100 CFU/m3 in the morning and 170 CFU/m3 in the afternoon with the mean estimate of 25 CFU/m3 in the morning and 42.5 CFU/m3 in the afternoon. The highest fungal load was equally estimated in the LAR at a percentage rate of 55% and 54.12% in the morning and afternoon, respectively. The results of the indoor air quality assessment of the different laboratory sections revealed a very low (<50 CFU/m3) to low (50-100 CFU/m3) degree of both fungal and bacterial air pollution within the sampling time. A total of 3 bacterial and 5 fungal species were isolated as follows: Staphylococcus aureus 16(61.5%), coagulase negative Staphylococcus species (CoNS) 7 (27%) and Bacillus species 3 (11.5%); Aspergillus flavus 7 (25%), Aspergillus niger 8 (28.5%), Penicillium chrysogenum 4 (14.3%), Rhizopus spp. 5 (17.9%) and Fusarium spp. 4 (14.3%). The levels of indoor airborne bacteria and fungi as revealed in this study were found to be within the acceptable and permissible limits of microbial load ≤500 CFU/m3.
Conclusion: Attention should be given to control those human, animal and environmental factors which favour the proliferation of bacteria and fungi in the indoor environment of school laboratories to safeguard the health of students, lecturers and laboratory personnel in the University.
Keywords: Microbial Quality, Indoor Air, Laboratory, Colony, Pollution
Galore Knowledge Publication Pvt. Ltd.
Title: Microbial Assessment of Indoor Air Quality of Laboratory Sections in Obong University, Obong Ntak, Nigeria
Description:
Background: Poor indoor air quality constitutes a significant health problem in schools, mostly in the laboratory sections due to a high number of students per laboratory vis-a-vis space confinement, insufficient outside air supply, poor construction and maintenance of laboratory buildings.
Aim: This study was carried out to assess the air quality and identify airborne bacteria and fungi in selected sections of Obong University Laboratory.
Materials and Methods: Institutional based study employing passive air sampling, settle plate or gravitational sampling method to collect airborne bacteria and fungi was conducted in 3 selected laboratory sections of the University.
Culture, isolation, colony count/air quality assessment and identification of airborne bacteria and fungi were done using standard methods.
Results: The mean bacterial load was 111.
75 CFU/m3 in the morning and 125.
25 CFU/m3 in the afternoon.
The highest and lowest bacterial loads were recorded at the Laboratory Animal Room (LAR) to be 165 CFU/m3 and 201 CFU/m3 in the morning and afternoon, respectively.
The total fungal load was 100 CFU/m3 in the morning and 170 CFU/m3 in the afternoon with the mean estimate of 25 CFU/m3 in the morning and 42.
5 CFU/m3 in the afternoon.
The highest fungal load was equally estimated in the LAR at a percentage rate of 55% and 54.
12% in the morning and afternoon, respectively.
The results of the indoor air quality assessment of the different laboratory sections revealed a very low (<50 CFU/m3) to low (50-100 CFU/m3) degree of both fungal and bacterial air pollution within the sampling time.
A total of 3 bacterial and 5 fungal species were isolated as follows: Staphylococcus aureus 16(61.
5%), coagulase negative Staphylococcus species (CoNS) 7 (27%) and Bacillus species 3 (11.
5%); Aspergillus flavus 7 (25%), Aspergillus niger 8 (28.
5%), Penicillium chrysogenum 4 (14.
3%), Rhizopus spp.
5 (17.
9%) and Fusarium spp.
4 (14.
3%).
The levels of indoor airborne bacteria and fungi as revealed in this study were found to be within the acceptable and permissible limits of microbial load ≤500 CFU/m3.
Conclusion: Attention should be given to control those human, animal and environmental factors which favour the proliferation of bacteria and fungi in the indoor environment of school laboratories to safeguard the health of students, lecturers and laboratory personnel in the University.
Keywords: Microbial Quality, Indoor Air, Laboratory, Colony, Pollution.
Related Results
Potable Water Sources, Household Hygiene, and Sanitation Practices in Ikpoba Okha LGA, Edo State: Implications for Public Health and Sustainable Water Management
Omoregie, Andrew Edosa.1 Omoregie Abieyuwa Peace2 Okoro, Enyinnaya Okoro.3
1 College of Medi
Potable Water Sources, Household Hygiene, and Sanitation Practices in Ikpoba Okha LGA, Edo State: Implications for Public Health and Sustainable Water Management
Omoregie, Andrew Edosa.1 Omoregie Abieyuwa Peace2 Okoro, Enyinnaya Okoro.3
1 College of Medi
BACKGROUND
Access to potable drinking water and sufficient sanitation continues to be an urgent global concern, particularly in developing regions where con...
Pengalaman Informasi Orang Kalang Kendal Tentang Tradisi Kalang Obong Sebagai Warisan Budaya Tak Benda Tradisi Kalang Obong
Pengalaman Informasi Orang Kalang Kendal Tentang Tradisi Kalang Obong Sebagai Warisan Budaya Tak Benda Tradisi Kalang Obong
Culture is rapidly developing nowadays with easy access to diverse informationanywhere. However, this development impacts the information experience of the Orang Kalang regarding t...
Removal of toxic vapors by oxidation: Development of laboratory test procedures for in-duct air cleaning systems
Removal of toxic vapors by oxidation: Development of laboratory test procedures for in-duct air cleaning systems
Exposure to volatile organic compounds (VOC) in workplaces can cause acute effects such as irritation of the skin, the eyes, the mouth, and the nose. Some products may also cause c...
Exposure of Elderly People to Indoor Air Pollutants in Wanxia Nursing Home
Exposure of Elderly People to Indoor Air Pollutants in Wanxia Nursing Home
The elderly residing in nursing homes are typically more advanced in age, have more health issues, and spend more time indoors than other elderly people. This study explored the in...
Indoor and outdoor air quality relationships modelling
Indoor and outdoor air quality relationships modelling
Particulate matter (PM) related ambient pollution has emerged as one of the most significant environmental and human health issues during the last decades. Thus, ambient PM concent...
Indoor air quality measurements in Hungarian residential buildings
Indoor air quality measurements in Hungarian residential buildings
Indoor air quality is a major part of indoor environmental quality and plays an important role in creating sustainable and healthy indoor environments. Well-being, health and comfo...
Analisis Bentuk Aransemen Lagu Anoman Obong Ciptaan Ranto Edi Gudel Untuk Paduan Suara Karya V. Mangunsongs
Analisis Bentuk Aransemen Lagu Anoman Obong Ciptaan Ranto Edi Gudel Untuk Paduan Suara Karya V. Mangunsongs
The song Anoman Obong by Ranto Edi Gudel is a song that uses Javanese. The song was arranged into a choir format by V. Mangunsongs. The arrangement by V. Mangunsongs in the song An...
Revealing Long-Term Indoor Air Quality Prediction: An Intelligent Informer-Based Approach
Revealing Long-Term Indoor Air Quality Prediction: An Intelligent Informer-Based Approach
Indoor air pollution is an urgent issue, posing a significant threat to the health of indoor workers and residents. Individuals engaged in indoor occupations typically spend an ave...