Testing of a Freeze-proof Condenser for the Tracker Thermal Control System on AMS-02
View through CrossRef
<div class="htmlview paragraph">The paper describes freezing and pressure tests required to develop a freeze-proof condenser for the Tracker Thermal Control System (TTCS). The TTCS is a mechanically pumped two-phase carbon-dioxide loop dedicated to control the temperature of the Tracker electronics. The TTCS is part of the Alpha Magnetic Spectrometer planned aboard the truss of the International Space Station (ISS). The TTCS collects the heat at two evaporators and rejects it at two radiators. In case of an accidental power-down of the AMS02 experiment, resulting in a loss of radiator heater control, the Tracker radiators and the connected TTCS-condensers may cool down as low as −120ºC, which is well below the CO<sub>2</sub>-freezing point (−56ºC@3MPa). During uncontrolled radiator heat-up and thawing of the solid CO<sub>2</sub>, liquid CO<sub>2</sub> can be trapped in between solid parts resulting in high pressures. To withstand these high pressures, a high-pressure resistant condenser has been developed. In order to verify the design it was needed to determine the maximum pressure inside the condenser during thawing. The pressure determination is performed by a dedicated test set-up with strain gauges.</div>
<div class="htmlview paragraph">The paper describes the test and the implications on the condenser design. After an introduction on AMS, a description of the test set-up is given, followed by details on the calibration of the pressure sensors. Subsequently the test and test results are described.</div>
<div class="htmlview paragraph">It is concluded that the pressure build up during thawing follows the CO<sub>2</sub> melting line found in the CO<sub>2</sub> 3-phase diagram. Therefore the condenser maximum design pressure directly follows from this diagram when the maximum unloaded condenser temperature is known. From thermal analyses this temperature was found to be −5 ºC leading to a condenser maximum design pressur e of 300 MPa. The condenser, comprising small diameter Inconel 718 tubing attached to a grooved aluminium plate (d<sub>in</sub> = 1.0mm, d<sub>out</sub> = 3.0mm) is shown -by accepted stress calculation methods- to withstand this pressure within applicable safety margins.</div>
Title: Testing of a Freeze-proof Condenser for the Tracker Thermal Control System on AMS-02
Description:
<div class="htmlview paragraph">The paper describes freezing and pressure tests required to develop a freeze-proof condenser for the Tracker Thermal Control System (TTCS).
The TTCS is a mechanically pumped two-phase carbon-dioxide loop dedicated to control the temperature of the Tracker electronics.
The TTCS is part of the Alpha Magnetic Spectrometer planned aboard the truss of the International Space Station (ISS).
The TTCS collects the heat at two evaporators and rejects it at two radiators.
In case of an accidental power-down of the AMS02 experiment, resulting in a loss of radiator heater control, the Tracker radiators and the connected TTCS-condensers may cool down as low as −120ºC, which is well below the CO<sub>2</sub>-freezing point (−56ºC@3MPa).
During uncontrolled radiator heat-up and thawing of the solid CO<sub>2</sub>, liquid CO<sub>2</sub> can be trapped in between solid parts resulting in high pressures.
To withstand these high pressures, a high-pressure resistant condenser has been developed.
In order to verify the design it was needed to determine the maximum pressure inside the condenser during thawing.
The pressure determination is performed by a dedicated test set-up with strain gauges.
</div>
<div class="htmlview paragraph">The paper describes the test and the implications on the condenser design.
After an introduction on AMS, a description of the test set-up is given, followed by details on the calibration of the pressure sensors.
Subsequently the test and test results are described.
</div>
<div class="htmlview paragraph">It is concluded that the pressure build up during thawing follows the CO<sub>2</sub> melting line found in the CO<sub>2</sub> 3-phase diagram.
Therefore the condenser maximum design pressure directly follows from this diagram when the maximum unloaded condenser temperature is known.
From thermal analyses this temperature was found to be −5 ºC leading to a condenser maximum design pressur e of 300 MPa.
The condenser, comprising small diameter Inconel 718 tubing attached to a grooved aluminium plate (d<sub>in</sub> = 1.
0mm, d<sub>out</sub> = 3.
0mm) is shown -by accepted stress calculation methods- to withstand this pressure within applicable safety margins.
</div>.
Related Results
Analisa Pengaruh Variasi Susunan Pipa Kondensor, Masa Refrigerant, dan Kecepatan Aliran Udara Kondensor Terhadap Performa Kulkas R-600a
Analisa Pengaruh Variasi Susunan Pipa Kondensor, Masa Refrigerant, dan Kecepatan Aliran Udara Kondensor Terhadap Performa Kulkas R-600a
This study aims to analyze the effects of condenser pipe configuration, refrigerant charge, and condenser airflow velocity on the performance of a refrigerator using R-600a refrige...
The CLIMIDSON Manual for Antimicrobial Stewardship Programmes in Nigerian Health Care Facilities
The CLIMIDSON Manual for Antimicrobial Stewardship Programmes in Nigerian Health Care Facilities
Antimicrobial stewardship (AMS) remains a cornerstone of efforts aimed at improving antimicrobial-related patient safety. It slows the development and spread of antimicrobial resi...
Thermal Effects in High Compactness CEA Stack
Thermal Effects in High Compactness CEA Stack
Thermal management is a pivotal aspect of stack durability and system operability. Consequently, understanding the thermal mapping within a stack based on its operating conditions ...
Development of antimicrobial stewardship competencies: A pan-Canadian framework for nurses
Development of antimicrobial stewardship competencies: A pan-Canadian framework for nurses
Background: Recent evidence highlights the critical influence nurses may have in antimicrobial stewardship (AMS). However, nurses’ express knowledge gaps and a lack of confidence i...
Development of antimicrobial stewardship competencies: A pan-Canadian framework for nurses
Development of antimicrobial stewardship competencies: A pan-Canadian framework for nurses
ABSTRACT
Background: Recent evidence highlights the critical influence nurses may have in antimicrobial stewardship (AMS). However, nurses’ express knowledge gaps and a lack of con...
Covid-19 Consumer Tracker Waves 1 – 4
Covid-19 Consumer Tracker Waves 1 – 4
Background The Food Standards Agency commissioned social research to develop its evidence base on issues affecting consumers and businesses in order to inform its COVID-19 response...
COVID-19 Consumer Tracker Waves 5 – 8
COVID-19 Consumer Tracker Waves 5 – 8
Background The Food Standards Agency commissioned social research to develop its evidence base on issues affecting consumers and businesses in order to inform its COVID-19 response...
COVID-19 Consumer Tracker Waves 1 and 2
COVID-19 Consumer Tracker Waves 1 and 2
Background The Food Standards Agency commissioned social research to develop its evidence base on issues affecting consumers and businesses in order to inform its COVID-19 response...