Grounding Analysis Based on Different Soil Characteristics in The Distribution System

View through CrossRef
This study aims to obtain the type of grounding and resistance value in the distribution system of medium voltage UP3 South Surabaya ducts. In addition, to see the magnitude of the comparative value of the results of the resistance analysis stimulates ETAP. In the South Surabaya UP3 medium voltage distribution system. PT. PLN (Persero) improves and optimizes service to all of its customers. The grounding system at PT PLN UP3 South Surabaya. The existing PLN UP3 South Surabaya must comply with PUIL regulations of 2011, and the value of land holdings must be no greater than 5 Ω. Of the 15 grounding points analyzed, there are 3 points whose grounding values do not meet the requirements of PUIL 2011, namely the grounding values are still above 5 Ω. The smallest grounding resistance value before adding the rod electrode is 1.1 Ω at the 3rd point or BD 313 and after adding one rod and then paralleling it, the resistance value drops to 0.55 Ω. For the largest grounding resistance at the point that meets the requirements, namely 4 Ω at the 9th point or BD 653 and after adding one rod and then parallelizing it, the resistance value drops to 1.75 Ω. ETAPsimulation, the simulation results are affected by the value of x direction and the depth of the conductor. In addition, the simulation results are affected by the size of the rod. ETAP simulation results, the touch tolerable is 587.6 volts and the step tolerable is 1948.6 volts. For the largest grounding resistance at the point that meets the requirements, namely 4 Ω at the 9th point or BD 653 and after adding one rod and then parallelizing it, the resistance value drops to 1.75 Ω. ETAP simulation, the simulation results are affected by the value of x direction and the depth of the conductor. In addition, the simulation results are affected by the size of the rod. ETAP simulation results, the touch tolerable is 587.6 volts and the step tolerable is 1948.6 volts. For the largest grounding resistance at the point that meets the requirements, namely 4 Ω at the 9th point or BD 653 and after adding one rod and then parallelizing it, the resistance value drops to 1.75 Ω. ETAP simulation, the simulation results are affected by the value of x direction and the depth of the conductor. In addition, the simulation results are affected by the size of the rod. ETAP simulation results, the touch tolerable is 587.6 volts and the step tolerable is 1948.6 volts.
Title: Grounding Analysis Based on Different Soil Characteristics in The Distribution System
Description:
This study aims to obtain the type of grounding and resistance value in the distribution system of medium voltage UP3 South Surabaya ducts.
In addition, to see the magnitude of the comparative value of the results of the resistance analysis stimulates ETAP.
In the South Surabaya UP3 medium voltage distribution system.
PT.
PLN (Persero) improves and optimizes service to all of its customers.
The grounding system at PT PLN UP3 South Surabaya.
The existing PLN UP3 South Surabaya must comply with PUIL regulations of 2011, and the value of land holdings must be no greater than 5 Ω.
Of the 15 grounding points analyzed, there are 3 points whose grounding values do not meet the requirements of PUIL 2011, namely the grounding values are still above 5 Ω.
The smallest grounding resistance value before adding the rod electrode is 1.
1 Ω at the 3rd point or BD 313 and after adding one rod and then paralleling it, the resistance value drops to 0.
55 Ω.
For the largest grounding resistance at the point that meets the requirements, namely 4 Ω at the 9th point or BD 653 and after adding one rod and then parallelizing it, the resistance value drops to 1.
75 Ω.
ETAPsimulation, the simulation results are affected by the value of x direction and the depth of the conductor.
In addition, the simulation results are affected by the size of the rod.
ETAP simulation results, the touch tolerable is 587.
6 volts and the step tolerable is 1948.
6 volts.
For the largest grounding resistance at the point that meets the requirements, namely 4 Ω at the 9th point or BD 653 and after adding one rod and then parallelizing it, the resistance value drops to 1.
75 Ω.
ETAP simulation, the simulation results are affected by the value of x direction and the depth of the conductor.
In addition, the simulation results are affected by the size of the rod.
ETAP simulation results, the touch tolerable is 587.
6 volts and the step tolerable is 1948.
6 volts.
For the largest grounding resistance at the point that meets the requirements, namely 4 Ω at the 9th point or BD 653 and after adding one rod and then parallelizing it, the resistance value drops to 1.
75 Ω.
ETAP simulation, the simulation results are affected by the value of x direction and the depth of the conductor.
In addition, the simulation results are affected by the size of the rod.
ETAP simulation results, the touch tolerable is 587.
6 volts and the step tolerable is 1948.
6 volts.

Related Results

PENGARUH KELEMBABAN TANAH TERHADAP TAHANAN PENTANAHAN STUDI KASUS PADA GARDU INDUK KEMAYORAN 150 kV
PENGARUH KELEMBABAN TANAH TERHADAP TAHANAN PENTANAHAN STUDI KASUS PADA GARDU INDUK KEMAYORAN 150 kV
Abstract The value of grounding resistance at the substation should be 0 Ω or less than 1 Ω. The value of grounding resistance is influenced by the resistivity and the ground...
Ecological soil physics as section of ecological soil science
Ecological soil physics as section of ecological soil science
Nowadays, there is a general penetration of ecology in other related sciences. Soil science is not an exception. To the evidence of this, the works of soil scientists may serve, th...
Grounding of the mobile radio nodes in soils with vertical differential electrophysical causes
Grounding of the mobile radio nodes in soils with vertical differential electrophysical causes
When using overestimated values of soil parameters, the calculated resistance of the grounding electrodes will be increased and a larger number of electrodes will be required. This...
Grounding Performance of Hydrogel, Silica Gel and Charcoal Ash as Additive Material in Grounding System
Grounding Performance of Hydrogel, Silica Gel and Charcoal Ash as Additive Material in Grounding System
Grounding enhancement materials (GEMs) are one of the additive materials which can change the grounding performance without lots of significant costs. The study aimed to assess the...
Performance Analysis and Optimization Designs for HVDC Grounding Electrodes
Performance Analysis and Optimization Designs for HVDC Grounding Electrodes
High voltage direct current(HVDC) grounding electrodes can provide a current-leakage channel for ground faults, ensuring HVDC systems’ safety and reliability. The HVDC grounding el...
Research on the Corrosion Impact of DC Grounding Electrode Current on Surrounding Tower Grounding Systems
Research on the Corrosion Impact of DC Grounding Electrode Current on Surrounding Tower Grounding Systems
With the widespread application of high-voltage direct current (HVDC) transmission technology, the corrosion of grounding systems in transmission towers caused by the ground curren...
Soil-Available Nutrients Associated with Soil Chemical and Aggregate Properties following Vegetation Restoration in Western Sichuan, China
Soil-Available Nutrients Associated with Soil Chemical and Aggregate Properties following Vegetation Restoration in Western Sichuan, China
The status and drivers of soil-available nutrients in plant-recovered soils are not fully understood, limiting our ability to explore the role of soil-available nutrients in soil g...

Back to Top